CBXi IP Controller |
CBXi Web UI
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
21
MAN
01
41
re
v 2
3
IP NETWORK
CONFIGURATION
This page allows basic
IP
configuration, identifying the current device on the
IP
network.
If your network has a
DHCP
server, click the
Automatic (DHCP)
box. You can then use
BACnet
discovery to
list controllers along with their IP addresses, and can use the hostname to identify the IP address of a
specific controller. By default, all
CBXi
devices leaving the factory are configured to use
DHCP
, and have a
hostname set to “
CBXi
” followed by the controller’s serial number –
e.g.
CBXi901004A
If your network does not have a
DHCP
server, then the
CBXi
controller will use a default
IP address
, which
is made up as follows:
•
The first byte of the
IP address
is set to
10
•
The 6 digits of the numerical part of the serial number grouped into 3 sets of 2 digits to form the last
3 bytes of the IP address.
For example,
CBXi
with serial number
901001A
will be allocated the default IP address of
10.90.10.01
. See
also
IP Address
input is also used to specify the
subnet
mask
on page 7 for a full explanation.
Recovery IP Address
If the primary IP cannot be reached
–
for example if the primary is set to automatic and there is no DHCP
server available, then the user must use the Recovery IP Address to access the Web UI and properly
configure the primary. The recovery is only designed for access to the web UI.
The factory default value is based on the serial number in the same way as the primary, but the Recovery
IP Address should
not
be changed or disabled unless it interferes with other network operations.
Note
: A button-press reset (see