Advant
®
Controller 450 User’s Guide
Chapter 2 Installation
2-90
3BSE 002 415R701 Rev A
4.
Make a suitable dump of the application program:
–
Always make a source code dump of the PC program (DUPCS).
–
If there is no change in the system software compatibility code, make a dump of the
total data base (DUTDB).
–
If there is a change in the system software compatibility code, make a source code
dump (DUDBS).
Source code is always an option, but it is more time-consuming.
5.
Shut down the controller (and thereby the entire process control) by switching the power
supply off. Use the circuit breaker S1 on the power switch unit(s) for mains A and
mains B. Do not disconnect mains C.
6.
Extract the program card on the Processor Module PM511 located in the controller
subrack. Use the release push button.
CAUTION
Do not forget the general rule: Reflect on the danger of ESD. Use the
grounded wristband.
7.
Insert the new program card.
CAUTION
At insertion, use the grounded wristband.
Start-up
Suitable data base and PC program dumps, per point 4 in the setup instructions above,
are presupposed.
The following instructions do not include any utilization of the new software functionality,
but only aim at restoring the “old” application. Enlargement of the application may require
redimensioning of the data base and the PC program tables as well. For relevant information on
these topics, look elsewhere in this manual or see separate documentation.
1.
Follow the general instructions given in
Section 2.6.7, Power-up Ahead of Program
2.
Perform the controller system configuration:
a.
Load the data base dump, LOTDB or TRDBS, as applicable.
3.
Perform configuration/application building:
a.
Load the PC program dump, TRPCS.
4.
Back up the entire RAM, DUAP.
5.
Disable working mode CONFIGURATION, DICONFIG.
In addition to those indications obtained at power-up:
–
All red LED F (Fault) on S100 I/O board fronts are switched off.
–
The yellow LEDs INIT and INHIB on S100 I/O Bus Extenders
(DSBC 174/DSBC 176) board front are switched off.
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...