Advant
®
Controller 450 User’s Guide
5-86
3BSE 002 415R701 Rev A
Additional Information for Redundant Processor Modules
A controller with redundant processor modules should be treated as a single system. Make the
following additional steps. The one processor module which is primary/backup is denoted
primary/backup all through.
1.
Stop the backup module
a.
Set the start mode selector on the backup module in position 2 (STOP)
b.
Depress the ENTER button on the backup module
2.
Follow the general instructions above for a single system
3.
By way of conclusion start the backup module
a.
Set the start mode selector on the backup module in the same position as the primary
b.
Depress the ENTER button on the backup module
5.6 CPU Load Measurement
When the Advant Controller 450 is executing the PC programs, the CPU load depends mainly
on the size and nature of the PC programs and, above all, on the cycle times chosen for the
various execution units.
Use the ANPER (ANalyze PERformance) command to investigate the actual load. Using its
indications of the system load as a basis, you can adjust, for example, the chosen cycle times
and thereby optimize the use of the available performance.
The ANPER command is made up of a number of options. The first choice is between analysis
of the load of the entire Advant Controller (system load) or the load per system part (task load).
Please refer to the separate reference manual AMPL Configuration Advant Controller 400
Series for further information of the different commands and their possibilities.
5.7 Backup
5.7.1 Backup of System
After important changes in the application program a backup copy of the data base content and
the PC program should be made. Different methods using different dump/load commands exist.
A survey of the available facilities are given in Section 2.4.2.6 Dumping and Loading.
Otherwise you are referred to the separate reference manual AMPL Configuration Advant
Controller 400 Series which describe the practical work.
5.7.2 Backup of Application
If you want to store your application in a flash card (PCMCIA) on the Advant Controller 400
Series, you can use an Advant Station 130 Engineering Station which provide the following:
•
AdvaBuild On-line Builder
•
A flash card interface and corresponding software, CardTalk.
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...