![ABB Advant Controller 450 Скачать руководство пользователя страница 105](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016105.webp)
$GYDQW
&RQWUROOHU8VHU¶V*XLGH
6HFWLRQ 3URFHVV,QWHUIDFH
3BSE 002 415R701 Rev A
1-75
$QDORJ0RGXOHV
The analog I/O modules all have galvanic isolation relative to chassis ground in a group of 4 or
8 channels. The modules have the standard set of module status indicators.
Open circuit detection is available for inputs and outputs configured for 4…20 mA and for the
RTD and TC inputs.
7DEOH 6$QDORJ0RGXOHV
0RGXOHW\SH
'HVFULSWLRQ
AI810
Analog Input 1 x 8 channels. 0(4)…20 mA, 0(2)…10V, 12 bit.,
0.1% Current shunt resistor is protected to 30 V.
Rated isolation voltage 50 V.
AI820
Analog Input differential 1 x 4 channels. -20…20 mA, -5...5 V,
-10…10 V, 12 bit + sign, 0.1 %, CMV 50 V.
Current shunt resistor is protected to 30 V.
Rated isolation voltage 50 V.
AI830
Analog Input 1 x 8 ch. Pt100 (-80... 80
o
C, -200... 250
o
C,
-200 ... 850
o
C), Ni100 (-60 ... 180
o
C), Ni120 (-80 ... 260
o
C),
Cu10 (-100 ... 260
o
C), Resistor (0 ... 400
Ω
), 14 bit.
Rated isolation voltage 50 V.
AI835
Analog Input 1 x 8 ch. Termo Couples (TC),
type B (0 ... 1820
o
C), type C (0 ... 2300
o
C),
type E (-270 ... 1000
o
C), type J (-210 ... 1200
o
C),
type K (-270 ... 1372
o
C), type N (-270 ... 1300
o
C),
type R (-50 ... 1768
o
C), type S (-50 ... 1768
o
C),
type T (-270 ... 400
o
C), linear -30 .... 75 mV, 14 bit.
Rated isolation voltage 50 V.
AI890
Analog Input, with Intrinsically safe interface 1 x 8 ch.
0 (4)...20mA, 12 bit, 0.1%
Rated isolation voltage 50 V.
AI895
Analog Input, with Intrinsically safe and HART interface,
0(4)...20mA, 12 bit, 0.1%
Rated isolation voltage 50 V.
AO810
Analog Output 1 x 8 channels, 0(4)…20 mA, 14 bit 0.1%
RL maximum 500/850 Ohms.
Rated isolation voltage 50 V.
AO820
Analog Output 4 x 1 channels, -20…20 mA, -10...10 V,
12 bit + sign, 0.1%, individually galvanical isolated.
Current output RL maximum 550 Ohms.
Voltage output RL minimum 2 kohms.
Rated isolation voltage 50 V.
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...