Advant
®
Controller 450 User’s Guide
Chapter 2 Installation
2-54
3BSE 002 415R701 Rev A
2.4.2.1 Power-up
If, for some reason, you desire a limited power-up, the minimum equipment necessary is:
•
Processor Module PM511 including a program card
•
Submodule Carrier SC5x0.
1.
Check that the circuit breakers on the power switch units are switched off.
There is one circuit breaker for mains A (labeled S1) and one for mains C (labeled F1).
Redundancy adds another circuit breaker for mains B (labeled S1).
Reflect the relevance of:
–
Power switch in the cabinet housing the controller subrack
–
Separate power switch in any cabinet housing S100 I/O subrack with object oriented
connection units (OOCU)
–
Separate power switch in physically distributed cluster of S100 I/O subrack.
2.
Set the start mode selector on Processor Module PM511 in 3 (CLEAR) position.
NOTE
The CLEAR position is the only possible choice when you power up for the
first time.
Repeat for an eventually redundant processor module.
3.
Set the switch on all bus extenders DSBC 174 in position RUN.
4.
Switch on the mains supply to the cabinet and check for correct mains voltage with a
multimeter at the connection terminals on the power switch unit. See the terminal diagram
form enclosed at delivery.
5.
Switch on the circuit breaker S1 on the power switch unit(s) in any order (mains A and B).
Also switch on the miniature circuit breaker F1 for mains C.
Several power switch and distribution units can exist in the controller cabinet or in
adjacent I/O cabinets.
6.
Check for the following positive indications of a successful power-up:
–
Distribution Unit SX554
green LED LIVE (24 V)
–
Regulator SR511
green LEDs 5 V and 2 V
–
Backup Power Supply SB511 (or SB510)
green LED IP
–
Processor Module PM511
green LED RUN
display ind. P2
(Indicating working mode P2, CONFIGURATION)
–
S100 I/O Bus Extenders DSBC 174 or DSBC 176
green LEDs RUN
and DC OK
–
Redundant Processor Module PM511 (BACKUP)
green LED RUN
display ind. b2...b1
(The backup unit starts in working mode b2, UPGRADING. After a while (
<
90s)
there is a transition to b1, STANDBY). If a redundant processor module is available,
and if both modules’ start mode selectors are set in 3 (CLEAR) position, then the left
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...