![ABB Advant Controller 450 Скачать руководство пользователя страница 262](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016262.webp)
$GYDQW
&RQWUROOHU8VHU¶V*XLGH
&KDSWHU &RQILJXUDWLRQ$SSOLFDWLRQ%XLOGLQJ
3-16
3BSE 002 415R701 Rev A
DSAO130A
DSTA 138, DSTK 221L5
DSTA 138 provides object oriented connection to DSAI 130A and DSAO 130A. Regarding
output features please refer to DSAO 130A using DSTA 181 above.
DSTY 101
With DSTY 101 (insulation amplifier), you can obtain insulation at individual input and output
channels. The insulation is obtained between primary and secondary sides and to the supply.
*XLGHOLQHV'LJLWDO,QSXWV
You can choose between scanned or interrupt-controlled inputs when you select the digital input
board. The different methods of reading inputs are as follows:
•
Scanned inputs
The software scans the digital input boards and updates the data base in
the Advant Controller 450 at regular intervals. This causes the load in the controller to
remain constant, irrespective of the frequency of change at the inputs.
•
Interrupt-controlled inputs
The data base in Advant Controller 450 is only updated when the values at the inputs are
changed. This gives more exact time-tagging with event handling of the inputs. Interrupt-
controlled inputs also mean a lower load with low to moderate frequency of change.
DSDI 110A
DSTD 150A / DSTD 190, DSTK 221L3
DSDI 110AV1
DSTD 150A/DSTD 190V1
DSTK221L3
Scanned or interrupt-controlled 24 V d.c. inputs. You can configure the inputs for pulse
catching, that is, with filter times of 100 ms at switch-on and 2 s at switch-off. This function is
especially well suited for setting keys (push buttons).
In the connection unit, the current supply is divided into two groups of 16 channels each.
Each group has a common 0 V. This does not prevent external voltage supply and fusing for
smaller groups of channels but naturally requires that the 0 V sides can be connected. The two
groups are galvanically isolated from the internal electronics.
DSDI 110A DSTK 226L3
DSDI 110AV1 DSTK 226L3
32 scanned or interrupt-controlled digital inputs. You can configure the inputs for pulse
catching, that is, with filter times of 100 ms at switch-on and 2 s at switch-off. This function is
especially well suited for setting keys (push buttons). You can connect up to four of the
connection units listed below to this board and cable. Division between the different connection
units is a free choice. The properties of the inputs are decided by the selected connection units.
Each connection unit contains eight inputs.
DSTD 195 (replacing DSTD W110)
A connection unit with eight inputs for 24 V d.c. All channels are galvanically isolated.
DSTD 196 (replacing DSTD W113)
DSTD 196P
A connection unit with eight inputs for 24 V d.c. The inputs have common 0V and bias of -24 V,
which means that there is 48 V over the connection. DSTD 196P has pluggable screw terminals.
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...