![ABB Advant Controller 450 Скачать руководство пользователя страница 71](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016071.webp)
$GYDQW
&RQWUROOHU8VHU¶V*XLGH
6HFWLRQ 3RZHU6XSSO\
3BSE 002 415R701 Rev A
1-41
0DLQV1HW)LOWHU
The CE-marked design provides a mains net filter for each supply A, B and C. The filter is
installed between the enclosure port and the mains power switch. The purpose is to minimize
the risk of interference and the emission of conducted radio frequency field.
The filter is adapted to the estimated load from the installed equipment.
0DLQV3RZHU6ZLWFKDQG'LVWULEXWLRQ
You use the power switch and distribution unit to connect and disconnect the
Advant Controller 450 system to the mains and for distribution of voltage to different units in
the cabinet. The power switch unit contains terminal blocks, miniature circuit breakers and
power outlets for, for example, power supply units.
Normally, a common circuit breaker disconnects the mains from all cabinets housing the
controller and the I/O installation, that is the “hard” related cabinets. Variants can exist. Please
refer to the actual delivery documentation for further information.
3RZHU6XSSO\
The power supply units provide the regulators in the subracks with 24 V unstabilized d.c.
voltage. They can also be used to supply other circuits which do not require stabilized 24 V
voltage such as sensors, indicators, and so on.
There are certain restrictions on utilizing a common power supply for the system itself and
external equipment. Please refer to
Section 3.1, Design Considerations
Use duplicated power supply units to provide redundancy.
Varying requirements on power supply are met by a range of supply modules with different
technical data. You can select according to
7DEOH 6HOHFWLRQ*XLGHRI3RZHU6XSSO\0RGXOHV
0RGXOHW\SH
DFGF
1HW
0D[ORDG
5HPDUNV
SA161
a.c.
120 V
24 V, 10 A
SA162
a.c.
230 V
24 V, 10 A
SA167
a.c.
120 V
24 V, 25 A
SA168
a.c.
230 V
24 V, 25 A
SD150
d.c.
24-48 V d.c.
24 V, 20 A
SA171
a.c.
120 V
48 V, 5 A
For field equipment only
SA172
a.c.
230 V
48 V, 5 A
For field equipment only
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...