Advant
®
Controller 450 User’s Guide
Section 2.2.10 S100 I/O
3BSE 002 415R701 Rev A
2-37
Readjustment
AO boards are factory adjusted for voltage output signals. If current signal is desired/jumpered,
you must readjust for maximum accuracy. Please follow the instructions found in
5.5.12, Channel Adjustment on AO Board
Preparation for Start-up
Check of the External Wiring
Judge the level of workmanship case by case. The result determines the need to thoroughly
check all connections before the system is powered up.
You can, of course, check with a buzzer or similar device that the external wiring to the process
equipment is correct and that all conductors are intact.
Without activating the control equipment, you can also check that transducers and actuators
(including all process wiring) function correctly. This makes it necessary to connect voltage to
these units and develop suitable checking methods, which are time-consuming activities.
An alternative method is to make an integrated check of the process equipment and wiring and
the corresponding controller function, which can be accomplished with a circuit-by-circuit
procedure. Preferably, the controller is loaded with application data base. The data base is then
used as one checkpoint. Status/values can be read and control signals to process objects can be
simulated by an engineering station. When an operator station is included in the system, it is
Table 2-3. Functional Jumpering
Board/Connection Unit
Function
DSAI 146, 155A
Mains frequency
DSTA 001, 001B, 002, 002B
Current/voltage
DSTA 131, 133, 135
Current/voltage, grounded/floated supply
DSTA 155, 155P, 156, 156B
Grounding
DSAO 110
Current/voltage, 10/20 mA, gain factor
DSAO 120A
Current/voltage
DSAO 130
Current/voltage, 10/20 mA
DSDP 140A
Filter time, function mode
DSDP 150
Function mode, voltage level
DSDP 170
Interrupt level, measuring interval source and
time, filter time for inputs
DSTX 170
Input signal level, grounding
DSDC 111
References
DSTX 110
External/internal supply
DSTY 101
Signal range
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...