![ABB Advant Controller 450 Скачать руководство пользователя страница 550](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016550.webp)
Advant
®
Controller 450 User’s Guide
Appendix I System Messages
I-22
3BSE 002 415R701 Rev A
Table I-13. Type 29, Code 1, 2, 3 and 4
Type Code
Significance
Address
Comments/Actions
29
1
Message from redundant
processor module
diagnostics
1
3
4
Changeover has been performed automatically.
Fault in backup processor module.
Diagnostics fault.
2
Memory error in processor
module RAM
1
2
The frequency of corrected bit-errors has exceeded a
certain limit. Data 1 = processor module position.
The total number of corrected bit errors has exceeded
a certain limit. Data 1 = processor module position.
Program card supervision
H’10
H’11
H’12
H’13
Correct program card (PCMCIA 2.0) replaced.
Program card memory checksum error.
Program card removed (missing card).
Wrong program card.
For the addresses H’10..H’13 data 1 and data 2 give
the position and subposition respectively.
3
Incorrect backup voltage for
RAM
1
Check battery backup.
4
Message from minute pulse
handler
1
2
No minute pulse available (
≥
3 pulses missing)
Minute pulse outside time range. Data 1 gives the
difference in units of 0.1 ms.
18:33:55
29
2
CXKK600
Type 29 Redundant Processor Modules, Operating System, Kernel
1
5
11
1
H’00000012
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...