• Symbol # represents trip units. Trip units allowed include A thru C, E thru L, P
thru Z. If using Ekip breakers, set the overload current of the circuit breaker
equal to or less than the value shown in the “CB Maximum Current” column in
the tables below.
• The digits indicated with an “*” represent accessories for the breakers and have
no impact on the drive UL listing or performance or rating of the breaker.
6. Ratings in the tables are maximum for the given circuit breaker frame size. Breakers
with lower current ratings are also allowed if they have the same frame size,
interrupting rating, and voltage rating.
7. Using a circuit breaker with a lower kAIC rating is not allowed even if the available
short-circuit current is less than 65 kA.
8. When designing UL 508A panels, Article SB 4.2.3 Exception No. 3 allows the use
of other manufacturers' current limiting inverse time circuit breakers which have the
same voltage, current and interrupting rating, if
I
peak
and
I
2
t
are the same or less
than the ABB specified circuit breaker.
9. Only current limiting inverse time circuit breakers can be used.
10. The drives listed below have no Enclosure Minimum Volume unlike 480 V and 600 V
ACS880-01 drives.
Max.
Ipeak
Max. I2t
ABB circuit breaker
Drive
volume
CB
Voltage
CB
Maxim-
um
cur-
rent
Input
cur-
rent
Frame
ACS880-
11-…
kA
A2s
in3
V
A
A
U
n = 480 V
23.2
0.512×106
XT2Hαβ020#********
1638
480
20
5.8
R3
07A6-5
23.2
0.512×106
XT2Hαβ020#********
1638
480
20
7.8
R3
11A0-5
23.2
0.512×106
XT2Hαβ035#********
1638
480
35
10.6
R3
014A-5
23.2
0.512×106
XT2Hαβ035#********
1638
480
35
15.6
R3
021A-5
23.2
0.512×106
XT2Hαβ070#********
3507
480
70
21.3
R6
027A-5
23.2
0.512×106
XT2Hαβ070#********
3507
480
70
26.2
R6
034A-5
23.2
0.512×106
XT2Hαβ070#********
3507
480
70
31.2
R6
040A-5
23.2
0.512×106
XT2Hαβ125#********
3507
480
125
40.1
R6
052A-5
23.2
0.512×106
XT2Hαβ125#********
3507
480
125
49.5
R6
065A-5
23.2
0.512×106
XT2Hαβ125#********
3507
480
125
60.2
R6
077A-5
30
0.98×106
XT4Hαβ225#********
6602
480
225
74
R8
101A-5
30
0.98×106
XT4Hαβ225#********
6602
480
225
100
R8
124A-5
30
0.98×106
XT4Hαβ250#********
6602
480
250
120
R8
156A-5
30
0.98×106
XT4Hαβ250#********
6602
480
250
147
R8
180A-5
3AXD50000645015
178 Technical data
Содержание ACS880-11
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 52: ...52 ...
Страница 82: ...82 ...
Страница 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Страница 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Страница 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Страница 112: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 112 Electrical installation IEC ...
Страница 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Страница 120: ...R3 7 7 8 8 L1 L2 L3 T1 U T2 V T3 W PE Ground 1 7 N m 1 2 lbf ft 120 Electrical installation North America NEC ...
Страница 142: ...142 ...
Страница 154: ... Fan arrow must point up 154 Maintenance ...
Страница 160: ...160 ...
Страница 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Страница 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Страница 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Страница 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Страница 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Страница 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Страница 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Страница 208: ...208 ...
Страница 225: ... Declarations of conformity The Safe torque off function 225 ...