■
gG fuses DIN 43620 blade style
gG fuses can be used for frames R3 and R6 if they operate rapidly enough (max. 0.1
seconds). ABB recommends, however, aR fuses. gG fuses are not allowed for frame
R8.
gG fuses (one fuse per phase)
Input cur-
rent
Min.
short-cir-
cuit cur-
rent1)
ACS880-
11-…
Size DIN
43620
ABB type
Voltage
rating
I2t
Nominal
current
V
A2s
A
A
A
3-phase
U
n = 400 V
000
OFAF000H16
500
700
16
8.0
120
09A4-3
000
OFAF000H16
500
700
16
10.0
120
12A6-3
000
OFAF000H25
500
2500
25
14.0
200
017A-3
000
OFAF000H32
500
4500
32
20.0
250
025A-3
000
OFAF000H40
500
7700
40
27.0
350
032A-3
000
OFAF000H50
500
15400
50
33.0
400
038A-3
000
OFAF000H63
500
21300
63
40.0
500
045A-3
000
OFAF000H80
500
37000
80
51.0
800
061A-3
000
OFAF000H100
500
63600
100
63.0
1000
072A-3
000
OFAF000H100
500
63600
100
76.0
1000
087A-3
3-phase
U
n = 500 V
000
OFAF000H16
500
700
16
5.8
120
07A6-5
000
OFAF000H16
500
700
16
7.8
120
11A0-5
000
OFAF000H25
500
2500
25
10.6
200
014A-5
000
OFAF000H32
500
4500
32
15.6
250
021A-5
000
OFAF000H40
500
7700
40
21.3
350
027A-5
000
OFAF000H50
500
15400
50
26.2
400
034A-5
000
OFAF000H63
500
21300
63
31.2
500
040A-5
000
OFAF000H80
500
37000
80
40.1
800
052A-5
000
OFAF000H100
500
63600
100
49.5
1000
065A-5
000
OFAF000H100
500
63600
100
60.2
1000
077A-5
1)
Minimum short-circuit current of the installation
■
Quick guide for selecting between gG and aR fuses
The combinations (cable size, cable length, transformer size and fuse type) in this table
fulfill the minimum requirements for the correct operation of the fuse. Use this table to
select between gG and aR fuses or calculate the short-circuit current of the installation
as described in section
Calculating the short-circuit current of the installation (page 174)
.
Technical data 173
Содержание ACS880-11
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 52: ...52 ...
Страница 82: ...82 ...
Страница 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Страница 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Страница 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Страница 112: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 112 Electrical installation IEC ...
Страница 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Страница 120: ...R3 7 7 8 8 L1 L2 L3 T1 U T2 V T3 W PE Ground 1 7 N m 1 2 lbf ft 120 Electrical installation North America NEC ...
Страница 142: ...142 ...
Страница 154: ... Fan arrow must point up 154 Maintenance ...
Страница 160: ...160 ...
Страница 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Страница 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Страница 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Страница 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Страница 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Страница 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Страница 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Страница 208: ...208 ...
Страница 225: ... Declarations of conformity The Safe torque off function 225 ...