Fuses (UL)
The UL Listed fuses in this manual are required for branch circuit protection and required
per NEC. The drives are suitable for use on a circuit capable of delivering not more than
100 kA symmetrical amperes (RMS) at 480 V maximum when protected by the fuses
described below.
Class T fuses are recommended below. Also allowed are UL Listed 248-8 Class J fast
acting, time delay, and high speed fuses, 248-4 Class CC fast acting fuses and 248-17
Class CF fast acting and time delay fuses of the same nominal voltage and current
rating.
Refer to notes below the tables.
UL (one fuse per phase)
Input current
ACS880-11-…
UL class
Bussmann
type
Voltage rating
Nominal cur-
rent
V
A
A
3-phase
U
n = 480 V
T
JJS-15
600
15
5,8
07A6-5
T
JJS-20
600
20
7,8
11A0-5
T
JJS-25
600
25
10,6
014A-5
T
JJS-35
600
35
15,6
021A-5
T
JJS-40
600
40
21,3
027A-5
T
JJS-50
600
50
26,2
034A-5
T
JJS-60
600
60
31,2
040A-5
T
JJS-80
600
80
40,1
052A-5
T
JJS-90
600
90
49,5
065A-5
T
JJS-110
600
110
60,2
077A-5
T
JJS-150
600
150
74
101A-5
T
JJS-200
600
200
100
124A-5
T
JJS-225
600
225
120
156A-5
T
JJS-300
600
300
147
180A-5
1. Fuses are required as part of the installation, are not included in the base drive
configuration and must be provided by others.
2. Fuses with a higher current rating than specified must not be used.
3. The UL listed fuses recommended by ABB are the required branch circuit protection
per NEC. Circuit breakers listed in section
Circuit breakers (UL)
are also acceptable
as branch circuit protection.
4. The recommended size or smaller UL listed 248 fast acting, time delay, or high
speed fuses must be used to maintain the UL listing of the drive. Additional protection
can be used. Refer to local codes and regulations.
176 Technical data
Содержание ACS880-11
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 52: ...52 ...
Страница 82: ...82 ...
Страница 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Страница 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Страница 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Страница 112: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 112 Electrical installation IEC ...
Страница 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Страница 120: ...R3 7 7 8 8 L1 L2 L3 T1 U T2 V T3 W PE Ground 1 7 N m 1 2 lbf ft 120 Electrical installation North America NEC ...
Страница 142: ...142 ...
Страница 154: ... Fan arrow must point up 154 Maintenance ...
Страница 160: ...160 ...
Страница 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Страница 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Страница 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Страница 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Страница 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Страница 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Страница 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Страница 208: ...208 ...
Страница 225: ... Declarations of conformity The Safe torque off function 225 ...