The line-side and motor-side converters have their own control programs. The parameters
of both programs can be viewed and changed using a control panel.
■
DC voltage boost function
The drive can boost their DC link voltage. In other words, it can increase the operating
voltage of the DC link from its default value.
To take the DC voltage boost function in use:
1. adjust the user DC voltage reference value (
94.22
) and
2. select the user-defined reference
(94.22)
as the source for the drive DC voltage
reference (
94.21
).
Benefits of the DC voltage boost function are:
• possibility to supply nominal voltage to the motor even when the supply voltage of
the drive is below the motor nominal voltage level
• compensation of voltage drop due to output filter, motor cable or input supply cables
• increased motor torque in the field weakening area (ie, when the drive operates the
motor in the speed range above the motor nominal speed)
• possibility to use a motor with higher nominal voltage than the actual supply voltage
of the drive. Example: A drive that is connected to 415 V can supply 460 V to a 460 V
motor.
For more information, see
ACS880-11, ACS880-31, ACS880-14, ACS880-34,
ACS880-17, ACS880-37 drives product note on DC voltage boost
(
[English]).
■
DC connection
You can connect drive frames R3 and R6 to a common DC system, see
Common DC
systems with ACS880-01, -04, -11, -14, -31 and -34 drives application guide
(
[English]).
Operation principle and hardware description 29
Содержание ACS880-11
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 52: ...52 ...
Страница 82: ...82 ...
Страница 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Страница 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Страница 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Страница 112: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 112 Electrical installation IEC ...
Страница 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Страница 120: ...R3 7 7 8 8 L1 L2 L3 T1 U T2 V T3 W PE Ground 1 7 N m 1 2 lbf ft 120 Electrical installation North America NEC ...
Страница 142: ...142 ...
Страница 154: ... Fan arrow must point up 154 Maintenance ...
Страница 160: ...160 ...
Страница 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Страница 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Страница 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Страница 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Страница 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Страница 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Страница 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Страница 208: ...208 ...
Страница 225: ... Declarations of conformity The Safe torque off function 225 ...