64 Guidelines for planning the electrical installation
Power cable types for restricted use
Not allowed power cable types
Motor cable shield
If the motor cable shield is used as the sole protective earth conductor of the motor, make
sure that the conductivity of the shield is sufficient. See subsection
above, or
IEC 61800-5-1. To effectively suppress radiated and conducted radio-frequency
emissions, the cable shield conductivity must be at least 1/10 of the phase conductor
conductivity. The requirements are easily met with a copper or aluminum shield. The
minimum requirement of the motor cable shield of the drive is shown below. It consists of a
concentric layer of copper wires with an open helix of copper tape or copper wire. The
better and tighter the shield, the lower the emission level and bearing currents.
Additional US requirements
Use type MC continuous corrugated aluminum armor cable with symmetrical grounds or
shielded power cable for the motor cables if metallic conduit is not used. For the North
American market, 600 V AC cable is accepted for up to 500 V AC. 1000 V AC cable is
required above 500 V AC (below 600 V AC). For drives rated over 100 amperes, the
power cables must be rated for 75 °C (167 °F).
Conduit
Couple separate parts of a conduit together: bridge the joints with a ground conductor
bonded to the conduit on each side of the joint. Also bond the conduits to the drive
enclosure and motor frame. Use separate conduits for input power, motor, brake resistor,
and control wiring. When conduit is employed, type MC continuous corrugated aluminum
armor cable or shielded cable is not required. A dedicated ground cable is always
required.
A four-conductor system (three phase conductors and a protective conductor on
a cable tray) is
not allowed for motor cabling
(allowed for input cabling).
Symmetrical shielded cable with individual shields for each phase conductor is
not allowed on any cable size for input and motor cabling.
1
Insulation jacket
2
Helix of copper tape or copper wire
3
Copper wire screen
4
Inner insulation
5
Cable core
PE
PE
1
3
4
5
2
Содержание ACS880-04F
Страница 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Страница 4: ......
Страница 24: ...24 Introduction to the manual ...
Страница 46: ...46 Guidelines for planning the mechanical installation ...
Страница 102: ...102 Installation checklist ...
Страница 106: ...106 Fault tracing ...
Страница 135: ...Technical data 135 Declaration of Conformity ...
Страница 136: ...136 Technical data ...
Страница 140: ...140 Technical data ...
Страница 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Страница 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Страница 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Страница 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Страница 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Страница 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Страница 148: ...148 Dimension drawings 3AXD50000038119 ...
Страница 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Страница 150: ...150 Dimension drawings ...
Страница 164: ...164 Safe torque off function ...