
120 Technical data
Definitions
When is derating needed
Derate the continuous output current of the drive if
•
ambient temperature e40 °C (+104 °F) or
•
drive is installed higher than 1000 m (3280 ft) above sea level
•
switching frequency is other than default.
Note:
The final derating factor is a multiplication of all applicable derating factors.
880A-5
R11
880
1100
1100
880
630
762
857
560
697**
500
3AXD00000588487
NEMA RATINGS
Drive type
ACS880-
04F-
Frame
size
Input
current
Maximum
current
Output ratings
App.
power
Light-duty use
Heavy-duty use
I
1
I
max
I
max_
start
S
N
I
Ld
P
Ld
I
Hd
P
Hd
A
A
A
kVA
A
kW
hp
A
kW
hp
U
N
= 460 V
502A-5
R11
502
560
671
435
483
315
400
361
250
300
582A-5
R11
582
730
828
504
573
400
450
414
250
350
634A-5
R11
634
730
954
549
623
450
500
477
315
400
715A-5
R11
715
850
1100
619
705
500
600
566
400
450
820A-5
R11
820
1020
1100
710
807
560
700
625
450
500
880A-5
R11
880
1100
1100
762
857
560
700
697**
500
600
U
N
Nominal voltage of the drive
I
1
Nominal input current (rms) at 40 °C (104 °F)
S
N
Apparent power (no overload)
I
max
Maximum output current. Available for 10 seconds at start, otherwise as long as allowed by
drive temperature. 140% … 200% of
I
Hd
, depending on power rating.
I
max_start
Maximum output current at start. Available for two seconds only at start every five seconds if
start current limit is activated by parameter
30.15 Maximum start current.
I
2
Continuous rms output current. No overload capability at 40 °C (104 °F)
P
N
Typical motor power in no-overload use.
I
Ld
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
P
Ld
Typical motor power for light-overload use.
I
Hd
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
*
Continuous rms output current allowing 40% overload for 1 minute every 5 minutes
**
Continuous rms output current allowing 45% overload for 1 minute every 5 minutes
P
Hd
Typical motor power for heavy-duty use.
Note:
To achieve the rated motor power given in the table, the rated current of the drive must be higher than
or equal to the rated motor current. The power ratings apply to most IEC 34 motors at the nominal voltage of
the drive.
We recommend to select the drive, motor and gear combination for the required motion profile with the
DriveSize dimensioning tool available from ABB.
IEC RATINGS
Drive type
ACS880-
04F-
Frame
size
Input
current
Output ratings
Nominal use
Light-duty use Heavy-duty use
I
1
I
max
I
max_
start
I
2
P
N
S
N
I
Ld
P
Ld
I
Hd
P
Hd
A
A
A
A
kW
kVA
A
kW
A
kW
Содержание ACS880-04F
Страница 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Страница 4: ......
Страница 24: ...24 Introduction to the manual ...
Страница 46: ...46 Guidelines for planning the mechanical installation ...
Страница 102: ...102 Installation checklist ...
Страница 106: ...106 Fault tracing ...
Страница 135: ...Technical data 135 Declaration of Conformity ...
Страница 136: ...136 Technical data ...
Страница 140: ...140 Technical data ...
Страница 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Страница 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Страница 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Страница 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Страница 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Страница 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Страница 148: ...148 Dimension drawings 3AXD50000038119 ...
Страница 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Страница 150: ...150 Dimension drawings ...
Страница 164: ...164 Safe torque off function ...