124 Technical data
High speed mode
Selection
High speed mode
of parameter
95.15 Special HW settings
improves control
performance at high output frequencies. We recommend it to be selected with output
frequency of 120 Hz and above.
This table gives the drive module ratings for 120 Hz output frequency and the maximum
output frequency for the drive ratings when
High speed mode
in parameter
95.15 Special
HW settings
is enabled: With output frequencies smaller than this recommended
maximum output frequency, the current derating is less than the values given in the table.
Contact ABB for operation above the recommended maximum output frequency or for the
output current derating with output frequencies above 120 Hz and below the maximum
output frequency.
Drive
module
type
ACS880-
04F-
Deratings with selection High speed mode of parameter 95.15 Special HW settings
120 Hz output frequency
Maximum output frequency
Nominal use
Light-
duty use
Heavy-
duty use
Nominal use
Light-
duty
use
Heavy-
duty use
f
I
N
P
N
I
Ld
I
Hd
f
max
I
N
P
N
I
Ld
I
Hd
Hz
A
kW
A
A
Hz
A
kW
A
A
U
N
= 400 V
504A-3
120
504
250
485
361
500
390
200
370
290
584A-3
120
584
315
575
429
500
437
250
419
311
649A-3
120
649
355
634
477
500
485
250
466
346
725A-3
120
725
400
715
566
500
519
250
496
390
820A-3
120
820
450
810
625
500
587
315
562
431
880A-3
120
880
500
865
725*
500
630
355
600
500*
U
N
= 500 V
459A-5
120
459
315
450
330
500
357
250
345
265
502A-5
120
502
355
483
361
500
390
250
370
290
582A-5
120
582
400
573
414
500
400
250
380
298
634A-5
120
634
450
623
477
500
410
250
392
298
715A-5
120
715
500
705
566
500
462
315
428
362
820A-5
120
820
560
807
625
500
530
355
490
400
880A-5
120
880
630
857
697***
500
550
400
510
410
3AXD00000588487
f
Output frequency
f
max
Maximum output frequency with High speed mode
U
N
Nominal voltage of the drive
I
N
Continuous rms output current. No overload capability at 40 °C (104 °F)
P
N
Typical motor power in no-overload use.
I
Ld
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
P
Ld
Typical motor power for light-overload use.
I
Hd
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
* Continuous rms output current allowing 40% overload for 1 minute every 5 minutes
*** Continuous rms output current allowing 45% overload for 1 minute every 5 minutes
Содержание ACS880-04F
Страница 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Страница 4: ......
Страница 24: ...24 Introduction to the manual ...
Страница 46: ...46 Guidelines for planning the mechanical installation ...
Страница 102: ...102 Installation checklist ...
Страница 106: ...106 Fault tracing ...
Страница 135: ...Technical data 135 Declaration of Conformity ...
Страница 136: ...136 Technical data ...
Страница 140: ...140 Technical data ...
Страница 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Страница 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Страница 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Страница 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Страница 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Страница 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Страница 148: ...148 Dimension drawings 3AXD50000038119 ...
Страница 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Страница 150: ...150 Dimension drawings ...
Страница 164: ...164 Safe torque off function ...