62 Guidelines for planning the electrical installation
Selecting the power cables
General rules
Select the input power and motor cables according to local regulations:
•
Select a cable capable of carrying the drive nominal current. See section
(page
) for the rated currents.
•
Select a cable rated for at least 70
°
C (158
°
F) maximum permissible temperature of
conductor in continuous use. For US, see
•
The inductance and impedance of the PE conductor/cable (grounding wire) must be
rated according to permissible touch voltage appearing under fault conditions (so that
the fault point voltage will not rise excessively when a ground fault occurs).
•
600 V AC cable is accepted for up to 500 V AC. 750 V AC cable is accepted for up to
600 V AC. For 690 V AC rated equipment, the rated voltage between the conductors
of the cable should be at least 1 kV.
Use symmetrical shielded motor cables (see page
). Ground motor cable shields 360° at
both ends. Keep the motor cable and its PE pigtail (twisted shield) as short as possible to
reduce high-frequency electromagnetic emissions.
Note
: When continuous metal conduit is employed, shielded cable is not required. The
conduit must have bonding at both ends.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable is
recommended.
Compared to a four-conductor system, the use of symmetrical shielded cable reduces
electromagnetic emission of the whole drive system as well as the stress on motor
insulation, bearing currents and wear.
Unless local wiring regulations state otherwise, the cross-sectional area of the protective
conductor must agree with the conditions that require automatic disconnection of the
supply required in 411.3.2. of IEC 60364-4-41:2005 and be capable of withstanding the
prospective fault current during the disconnection time of the protective device.
The cross-sectional area of the protective conductor can either be selected from the table
below or calculated according to 543.1 of IEC 60364-5-54.
This table shows the minimum cross-sectional area related to the phase conductor size
according to IEC 61800-5-1 when the phase conductor and the protective conductor are
made of the same metal. If this is not so, the cross-sectional area of the protective earthing
conductor shall be determined in a manner which produces a conductance equivalent to
that which results from the application of this table.
Cross-sectional area of the phase conductors
S (mm
2
)
Minimum cross-sectional area of the
corresponding protective conductor
S
p
(mm
2
)
S < 16
S
16 < S < 35
16
35 < S
S/2
Содержание ACS880-04F
Страница 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Страница 4: ......
Страница 24: ...24 Introduction to the manual ...
Страница 46: ...46 Guidelines for planning the mechanical installation ...
Страница 102: ...102 Installation checklist ...
Страница 106: ...106 Fault tracing ...
Страница 135: ...Technical data 135 Declaration of Conformity ...
Страница 136: ...136 Technical data ...
Страница 140: ...140 Technical data ...
Страница 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Страница 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Страница 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Страница 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Страница 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Страница 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Страница 148: ...148 Dimension drawings 3AXD50000038119 ...
Страница 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Страница 150: ...150 Dimension drawings ...
Страница 164: ...164 Safe torque off function ...