58 Guidelines for planning the electrical installation
Selecting the supply disconnecting device
Install a hand-operated input disconnecting device between the AC power source and the
drive. The disconnecting device must be of a type that can be locked to the open position
for installation and maintenance work.
European Union
To agree with the European Union Directives, according to standard EN 60204-1,
Safety of
Machinery
, the disconnecting device must be one of the following types:
•
switch-disconnector of utilization category AC-23B (EN 60947-3)
•
disconnector that has an auxiliary contact that in all cases causes switching devices to
break the load circuit before the opening of the main contacts of the disconnector
(EN 60947-3)
•
circuit breaker suitable for isolation in accordance with EN 60947-2.
Other regions
The disconnecting device must conform to the applicable safety regulations.
Selecting the main contactor
If a main contactor is used, its utilization category (number of operations under load) must
be AC-1 according to IEC 60947-4,
Low-voltage switchgear and controlgear
. Select the
contactor according to the nominal voltage and current of the drive.
Examining the compatibility of the motor and drive
Use an asynchronous AC induction motor, permanent magnet motor, AC induction
servomotor or ABB synchronous reluctance motor (SynRM motor) with the drive. Several
induction motors can be connected at a time.
Select the motor size and drive type from the rating tables in chapter
on
basis of the AC line voltage and motor load. Use the DriveSize PC tool if you need to tune
the selection more in detail.
Make sure that the motor withstands the maximum peak voltage in the motor terminals,
see the
. For basics of protecting the motor insulation and
bearings in drive systems, refer to section
Protecting the motor insulation and bearings
below.
Note:
•
Consult the motor manufacturer before you use a motor which nominal voltage differs
from the AC line voltage connected to the drive input.
•
The voltage peaks at the motor terminals are relative to the supply voltage of the drive,
not the drive output voltage.
•
If the motor and drive are not of the same size, consider the following operation limits
of the drive control program:
•
motor nominal voltage range 1/6 ... 2 ·
U
N
•
motor nominal current range 1/6 ... 2 ·
I
N
of the drive in DTC control and 0 ... 2 ·
I
N
in scalar control. The control mode is selected by a drive parameter.
Содержание ACS880-04F
Страница 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Страница 4: ......
Страница 24: ...24 Introduction to the manual ...
Страница 46: ...46 Guidelines for planning the mechanical installation ...
Страница 102: ...102 Installation checklist ...
Страница 106: ...106 Fault tracing ...
Страница 135: ...Technical data 135 Declaration of Conformity ...
Страница 136: ...136 Technical data ...
Страница 140: ...140 Technical data ...
Страница 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Страница 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Страница 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Страница 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Страница 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Страница 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Страница 148: ...148 Dimension drawings 3AXD50000038119 ...
Страница 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Страница 150: ...150 Dimension drawings ...
Страница 164: ...164 Safe torque off function ...