61
RUNNING
BOOL
FALSE = Drive is not running, TRUE = Drive is running and following the
speed reference value.
FAULT
BOOL
FALSE = No drive fault active, TRUE = Drive fault active.
WARN
BOOL
FALSE = No drive warning active, TRUE = Drive warning active.
EXT_RUN_ENABLE
BOOL
FALSE = No external run enable signal received in the drive, TRUE =
External run enable signal received in the drive.
LOCAL_CTRL
BOOL
FALSE=Remote control (normal mode), TRUE=Local control (e.g. drive
control panel or pc tool in local mode)
EXT_CTRL_LOC2
BOOL
Actual control place, FALSE = EXT1, TRUE = EXT2.
ACT_SPEED
INT
Drive actual speed: -20000 to 20000. S
ee chapter “Drive configuration”
for scaling.
MSW
WORD
Drive main status word. See actual fieldbus adapter manual for detailed
description.
MCW
WORD
Drive main control word. See actual fieldbus adapter manual for detailed
description.
Save your program.
Figure 33 Save program
Setting the drive in standby mode
Set
EMCY_STOP = TRUE
(deactivate emergency stop) and after that
SWITCH_ON = TRUE
to set the
drive in standby mode waiting for START command. To make the drive ready for start,
SWITCH_ON
always needs a positive edge after
EMCY_STOP
has been activated.
Figure 34 Standby mode
Содержание ACS355 series
Страница 1: ...Quick start up guide ABB Drives function blocks for Siemens PLC s...
Страница 76: ...A new subnet and IP protocol is added Figure 56 IP added...
Страница 84: ...9 Click to download the configuration to PLC Figure 73 Download to device...
Страница 139: ...139 Contact us www abb com drives www abb com drivespartners 3AXD50000037864 Rev B EN 2018 02 07...