ACS850 Minimum required parameter settings for PROFIBUS DP
The minimum required parameter settings based on factory default settings.
Parameter
Description
Setting
Comment
50.01
Fba enable
Enable
Activates fieldbus module.
51.05
PROFILE
1
Communication profile ABB drives.
10.01
Ext1 start func
FB
Fieldbus interface as source for start and stop.
21.01
Speed ref1 sel
FBA ref1
Fieldbus interface as source for speed reference.
10.10
Fault reset sel
P.02.22 bit 8
Fieldbus interface as source for fault reset.
(19.01)
Speed scaling
[Scale max]
Max speed/frequency scaling value (used in function
block/visualization input
SPEED_REF_MAX
). Must
be less or equal to drive parameter max
speed/frequency.
Starting ACS850 drives for PROFINET
1. Power up the drive.
2. Enable the communication between the adapter module and the drive by setting parameter
50.01
FBA enable
to Enable.
3. Select how the drive reacts to a fieldbus communication break with the parameter
50.02 Comm loss
func
.
Note:
This function monitors both communication between the fieldbus master and the adapter
module and communication between the adapter module and the drive.
4. With parameter
50.03 Comm loss t out
, define the time between communication break detection and
the selected action.
5. Select application-specific values for parameters
50.04
…
50.11
.
6. Set the FENA configuration parameters in group 51. At the minimum, set parameters
51.01 FBA A
type
as Ethernet,
51.02 Protocol/Profile
as PNIO ABB Pro (11),
51.04 IP configuration
as Static, and
required IP address from parameter
51.05
to parameter
51.08
and
51.09 Subnet CDR
as 24.
7. Define the process data transferred to and from the drive in the FBA-01 configuration parameter
groups 52 and 53.
Note:
The adapter module sets the Status word and actual value automatically in parameters
52.01
and
52.02
, and Control word and reference in parameters 53.01 and 53.02.
8. Validate the settings made in parameter groups 51, 52 and 53 by setting parameter
51.27 FBA par
refresh
to Refresh.
9. Set the relevant drive control parameters to control the drive according to the application.
Содержание ACS355 series
Страница 1: ...Quick start up guide ABB Drives function blocks for Siemens PLC s...
Страница 76: ...A new subnet and IP protocol is added Figure 56 IP added...
Страница 84: ...9 Click to download the configuration to PLC Figure 73 Download to device...
Страница 139: ...139 Contact us www abb com drives www abb com drivespartners 3AXD50000037864 Rev B EN 2018 02 07...