37
ACS880 Minimum required parameter settings for PROFINET
The minimum required parameter settings based on factory default settings.
Parameter
Description
Setting
Comment
50.01
FBA A Enable
Enable
Activates fieldbus module.
51.01
FBA A ype
Ethernet
Filedbus type.
51.02
Protocol/Profile
PNIO ABB Pro (11)
Communication profile ABB drives.
51.04
IP Configuration
Static (0)
-
51.05 ...
51.08
IP address
192.xxx.xx.xx or any other
required IP address.
-
51.09
Subnet CDR
24
24 For subnet mask 255.255.255.0.
51.27
FBA PAR
REFRESH
REFRESH
Updates fieldbus settings (groups 51
to 55).
20.01
Ext 1 commands
Fieldbus A
Fieldbus interface as source for start
and stop.
22.11
Speed ref1
selection
FB A ref1
Fieldbus interface as source for
speed reference.
31.11
Fault reset
selection
P.06.01 bit 7
Fieldbus interface as source for fault
reset.
(46.01)
Speed scaling
[Scale max]
Max speed/frequency scaling value
(used in function block/visualization
input
SPEED_REF_MAX
). Must be
less or equal to drive parameter max
speed/frequency.
ACS880 More parameters read from drive to PLC (optional)
Parameter
Description
Setting
Comment
52.03
…
52.12
Actual value or
parameter of drive
GGii
GG = parameter group, ii = parameter index
example, 0107 = actual current; 3501 = motor est.
temp
51.27
FBA PAR
REFRESH
REFRESH
Updates fieldbus settings (groups 50 to 57)
Содержание ACS355 series
Страница 1: ...Quick start up guide ABB Drives function blocks for Siemens PLC s...
Страница 76: ...A new subnet and IP protocol is added Figure 56 IP added...
Страница 84: ...9 Click to download the configuration to PLC Figure 73 Download to device...
Страница 139: ...139 Contact us www abb com drives www abb com drivespartners 3AXD50000037864 Rev B EN 2018 02 07...