ACS580 More parameters read from drive to PLC (optional)
Parameter
Description
Setting
Comment
52.03
…
52.12
Actual value or
parameter of drive
GGii
GG = parameter group, ii = parameter index
Example, 0107 = actual current; 3501 = motor est.
temp
51.27
FBA PAR
REFRESH
REFRESH
Updates fieldbus settings (groups 50 to 57)
ACS580 More parameters written from PLC to drive (optional)
Parameter
Description
Setting
Comment
53.03
…
53.12
Parameter of
drive
GGii
GG = parameter group, ii = parameter index
Example, 2312 = acceleration time 1
51.27
FBA PAR
REFRESH
REFRESH
Updates fieldbus settings (groups 50 to 57)
Configuring ACS800 drives
Starting ACS800 drives for PROFIBUS DP
1. Power up the drive.
2. Enable the communication between the adapter module and the drive by setting parameter
98.02
COMM. MODULE LINK
to FIELDBUS.
3. Set the RPBA-01 configuration parameters in group 51. At the minimum, set the required node
address in parameter
51.02
.
4. With parameter
30.18 COMM FLT FUNC
, select how the drive reacts to a fieldbus communication
break.
5. With parameter
30.19 MAIN REF DS T-OUT
, define the time between communication break detection
and the selected action.
6. Define the process data transferred to and from the drive in the RPBA-01 configuration parameter
group 51.
Note:
The Status Word, Actual Speed, Control Word and Speed Reference are configured as default.
7. Validate the settings made in parameter group 51 by setting parameter 51.27 FBA PAR REFRESH to
REFRESH.
8. Set the relevant drive control parameters to control the drive according to the application.
Содержание ACS355 series
Страница 1: ...Quick start up guide ABB Drives function blocks for Siemens PLC s...
Страница 76: ...A new subnet and IP protocol is added Figure 56 IP added...
Страница 84: ...9 Click to download the configuration to PLC Figure 73 Download to device...
Страница 139: ...139 Contact us www abb com drives www abb com drivespartners 3AXD50000037864 Rev B EN 2018 02 07...