ACS580 Minimum required parameter settings for PROFIBUS DP
The minimum required parameter settings based on factory default settings.
Parameter
Description
Setting
Comment
50.01
FBA A Enable
Enable
Activates fieldbus module
51.02
NODE
ADDRESS
[PB NODE]
PROFIBUS DP node address of the drive
51.05
PROFILE
1
Communication profile ABB drives
52.02
FBA data in2
Act1 16bit (5)
Actual speed as Data Word 2 from the drive
53.02
FBA data out2
Ref1 16bit (2)
Speed reference as Data Word 2 to the drive
51.27
FBA par refresh
Configure
Updates fieldbus settings (groups 50 to 57)
20.01
Ext 1 commands
Fieldbus A
Fieldbus interface as source for start and stop
22.11
Ext1 speed ref1
FB A ref1
Fieldbus interface as source for speed reference
31.11
Fault reset
selection
P.06.01 bit 7
Fieldbus interface as source for fault reset
(46.01)
Speed scaling
[Scale max]
Max speed/frequency scaling value (used in function
block/visualization input
SPEED_REF_MAX
). Must be
less or equal to drive parameter max speed/frequency.