Installation 97
External power supply for the JCU control unit (XPOW)
Ex24 V (minimum 1.6 A) power supply for the control unit can be connected to
terminal block XPOW. Using an external supply is recommended if
•
the application requires fast start after connecting the drive to the main supply
•
fieldbus communication is required when the input power supply is disconnected.
DI5 (XDI:5) as a thermistor input
1…3 PTC sensors can be connected to this input for motor temperature measurement.
Notes
:
•
Do not connect both ends of the cable shields directly to ground. If a capacitor cannot
be used at one end, leave that end of the shield unconnected.
•
The connection of temperature sensors involves parameter adjustment. See the
Firmware manual
of the drive.
•
Pt100 sensors are not to be connected to the thermistor input. Instead, an analog
input and an analog current output (located either on the JCU or on an I/O extension
module) are used as shown below. The analog input must be set to voltage.
Motor
T
Motor
T
T
T
XDI:5
XD24:1
3.3 nF
> 630 V AC
XDI:5
XD24:1
3.3 nF
> 630 V AC
One sensor
Three sensors
Motor
T
Motor
T
T
T
AI1+ (U)
AI1- (U)
3.3 nF
> 630 VAC
AOx (I)
AGND
AOx (I)
AGND
AI1+ (U)
AI1- (U)
One Pt100 sensor
Three Pt100 sensors
3.3 nF
> 630 VAC
Содержание ACQ810-04
Страница 1: ...ABB industry specific drives Hardware manual ACQ810 04 drive modules 200 to 500 kW 300 to 700 hp ...
Страница 4: ......
Страница 10: ...10 ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Planning the cabinet installation ...
Страница 75: ...Installation 75 Assembly drawing frame G1 ...
Страница 76: ...76 Installation Assembly drawing frame G2 ...
Страница 83: ...Installation 83 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Страница 84: ...84 Installation Assembly drawing of installing the drive module to the cabinet frame G1 ...
Страница 85: ...Installation 85 Assembly drawing of installing the drive module to the cabinet frame G2 ...
Страница 89: ...Installation 89 3AUA0000038989 TXD transmitter RXD receiver JRIB V2 V1 V7 V6 1 2 APOW 2 JINT 3 JRIB 1 4 4 JGDR ...
Страница 100: ...100 Installation ...
Страница 104: ...104 Installation checklist ...
Страница 106: ...106 Start up ...
Страница 108: ...108 Fault tracing ...
Страница 128: ...128 Technical data ...
Страница 130: ...130 Dimension drawings Frame G1 Drive module dimensions ...
Страница 131: ...Dimension drawings 131 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Страница 132: ...132 Dimension drawings ...
Страница 133: ...Dimension drawings 133 Frame G1 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Страница 134: ...134 Dimension drawings Frame G2 Drive module dimensions ...
Страница 135: ...Dimension drawings 135 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Страница 136: ...136 Dimension drawings ...
Страница 137: ...Dimension drawings 137 Frame G2 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Страница 138: ...138 Dimension drawings Bottom plate ...
Страница 142: ...142 du dt filters ...
Страница 144: ...3AUA0000120538 Rev A EN 2012 06 27 Contact us www abb com drives www abb com drivespartners ...