78 Installation
Power cable connection procedure
WARNING!
Follow the instructions in chapter
. Ignoring the
instructions can cause physical injury or death, or damage to the equipment.
1. Lead the input cables into the inside of the cabinet. Ground the cable shield 360° at
the lead-through plate.
2. Twist the cable shields of the input cables into bundles and connect them and any
separate ground conductors or cables to the PE (ground) terminal of the input power
cabling panel.
3. Connect the phase conductors of the input cables to terminals U1, V1 and W1 of the
input cabling panel. For the tightening torques, see page
4. Lead the motor cables into the inside of the cabinet. Ground the cable shield 360° at
the lead-through plate.
5. Twist the cable shields of the motor cables into bundles and connect them and any
separate ground conductors or cables to the PE (ground) terminal of the output power
cabling panel.
6. Connect the phase conductors of the motor cables to terminals U2, V2, W2
of the
output cabling panel. For the tightening torques, see page
.
1
For alternatives, see section
Selecting the supply disconnecting device
on page
43.
In the mounting
example of this chapter, the disconnecting device is not in the same cubicle with the drive module.
2
If a shielded cable is used (not required but recommended) and the conductivity of the shield is
< 50% of the conductivity of the phase conductor, use a separate PE cable (2a) or a cable with a
grounding conductor (2b).
3
360-degree grounding is recommended at the cabinet entry if a shielded cable is used. Ground the
other end of the input cable shield or PE conductor at the distribution board.
4
Input and output power cabling panels (H381)
5
360-degree grounding at the cabinet entry is recommended, see page
35.
6
Use a separate grounding cable if the conductivity of the cable shield is < 50% of the conductivity of
the phase conductor and there is no symmetrically constructed grounding conductor in the cable
(see page
7
Common mode filter, see page
.
8
d
u
/d
t
filter (optional, see page
9
The drive module frame must be connected to the cabinet frame. See section
on page
Note:
If there is a symmetrically constructed grounding conductor in the motor cable in addition to the conductive
shield, connect the grounding conductor to the grounding terminal at the drive and motor ends.
Do not use an asymmetrically constructed motor cable. Connecting its fourth conductor at the motor end
increases bearing currents and causes extra wear.
Содержание ACQ810-04
Страница 1: ...ABB industry specific drives Hardware manual ACQ810 04 drive modules 200 to 500 kW 300 to 700 hp ...
Страница 4: ......
Страница 10: ...10 ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Planning the cabinet installation ...
Страница 75: ...Installation 75 Assembly drawing frame G1 ...
Страница 76: ...76 Installation Assembly drawing frame G2 ...
Страница 83: ...Installation 83 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Страница 84: ...84 Installation Assembly drawing of installing the drive module to the cabinet frame G1 ...
Страница 85: ...Installation 85 Assembly drawing of installing the drive module to the cabinet frame G2 ...
Страница 89: ...Installation 89 3AUA0000038989 TXD transmitter RXD receiver JRIB V2 V1 V7 V6 1 2 APOW 2 JINT 3 JRIB 1 4 4 JGDR ...
Страница 100: ...100 Installation ...
Страница 104: ...104 Installation checklist ...
Страница 106: ...106 Start up ...
Страница 108: ...108 Fault tracing ...
Страница 128: ...128 Technical data ...
Страница 130: ...130 Dimension drawings Frame G1 Drive module dimensions ...
Страница 131: ...Dimension drawings 131 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Страница 132: ...132 Dimension drawings ...
Страница 133: ...Dimension drawings 133 Frame G1 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Страница 134: ...134 Dimension drawings Frame G2 Drive module dimensions ...
Страница 135: ...Dimension drawings 135 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Страница 136: ...136 Dimension drawings ...
Страница 137: ...Dimension drawings 137 Frame G2 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Страница 138: ...138 Dimension drawings Bottom plate ...
Страница 142: ...142 du dt filters ...
Страница 144: ...3AUA0000120538 Rev A EN 2012 06 27 Contact us www abb com drives www abb com drivespartners ...