Planning the cabinet installation 35
Planning the cabinet placement on a cable channel
Note the following when planning to place the cabinet on a cable channel:
•
The cabinet structure must be sturdy enough. If the whole cabinet base will not be
supported from below, the cabinet weight will lie on the sections that the floor carries.
•
Equip the cabinet with a sealed bottom plate and cable lead-throughs to ensure the
degree of protection and to prevent the cooling air flow from the cable channel into the
cabinet.
Planning the electromagnetic compatibility (EMC) of the
cabinet
Note following when planning the electromagnetic compatibility of the cabinet:
•
Generally, the fewer and smaller the holes in the cabinet, the better the interference
attenuation. The maximum recommended diameter of a hole in galvanic metal contact
in the covering cabinet structure is 100 mm (3.94 in). Pay special attention to the
cooling air inlet and outlet gratings.
•
The best galvanic connection between the steel panels is achieved by welding them
together as no holes are necessary. If welding is not possible, the seams between the
panels
are recommended to be left unpainted
and equipped with special conductive
EMC strips to provide adequate galvanic connection. Usually, reliable strips are made
of flexible silicon mass covered with a metal mesh. The non-tightened touch-contact of
the metal surfaces is not sufficient, so a conductive gasket between the surfaces is
required. The maximum recommended distance between assembly screws is 100 mm
(3.94 in).
•
Construct sufficient high-frequency grounding network in the cabinet to avoid voltage
differences and forming of high-impedance radiator structures. A good high-frequency
The carrying structure on a cable channel
Cabinet side view with a bottom plate
Содержание ACQ810-04
Страница 1: ...ABB industry specific drives Hardware manual ACQ810 04 drive modules 200 to 500 kW 300 to 700 hp ...
Страница 4: ......
Страница 10: ...10 ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Planning the cabinet installation ...
Страница 75: ...Installation 75 Assembly drawing frame G1 ...
Страница 76: ...76 Installation Assembly drawing frame G2 ...
Страница 83: ...Installation 83 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Страница 84: ...84 Installation Assembly drawing of installing the drive module to the cabinet frame G1 ...
Страница 85: ...Installation 85 Assembly drawing of installing the drive module to the cabinet frame G2 ...
Страница 89: ...Installation 89 3AUA0000038989 TXD transmitter RXD receiver JRIB V2 V1 V7 V6 1 2 APOW 2 JINT 3 JRIB 1 4 4 JGDR ...
Страница 100: ...100 Installation ...
Страница 104: ...104 Installation checklist ...
Страница 106: ...106 Start up ...
Страница 108: ...108 Fault tracing ...
Страница 128: ...128 Technical data ...
Страница 130: ...130 Dimension drawings Frame G1 Drive module dimensions ...
Страница 131: ...Dimension drawings 131 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Страница 132: ...132 Dimension drawings ...
Страница 133: ...Dimension drawings 133 Frame G1 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Страница 134: ...134 Dimension drawings Frame G2 Drive module dimensions ...
Страница 135: ...Dimension drawings 135 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Страница 136: ...136 Dimension drawings ...
Страница 137: ...Dimension drawings 137 Frame G2 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Страница 138: ...138 Dimension drawings Bottom plate ...
Страница 142: ...142 du dt filters ...
Страница 144: ...3AUA0000120538 Rev A EN 2012 06 27 Contact us www abb com drives www abb com drivespartners ...