50 Planning the electrical installation
Typical power cable sizes
The table below gives copper and aluminium cable types with concentric copper shield for
the drives with nominal current. See also
Terminal and lead-through data for the power
on page
121.
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three
ladder type trays one on top of the other, ambient temperature 30 °C (86
°
F) PVC
insulation, surface temperature 70 °C (158
°
F) (EN 60204-1 and IEC 60364-5-52). For
other conditions, dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive
.
2) The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F) ambient temperature. Not more than three current-
carrying conductors in raceway or cable or earth (directly buried). For other conditions,
dimension the cables according to local safety regulations, appropriate input voltage
and the load current of the drive.
ACQ810-04
IEC
1)
US
2)
Cu cable type Al cable type
Cu cable type
Al cable type
mm
2
mm
2
AWG/kcmil
AWG/kcmil
-377A-4
2 × (3×120)
3 × (3×120)
2 × 250 MCM
2 × 350 MCM
-480A-4
3 × (3×95)
3 × (3×150)
2 × 500 MCM or 3 × 250 MCM 2 × 600 MCM or 3 × 300 MCM
-570A-4
3 × (3×120)
3 × (3×185)
2 × 500 MCM or 3 × 250 MCM 2 × 700 MCM or 3 × 350 MCM
-634A-4
3 × (3×150)
3 × (3×240)
2 × 600 MCM or 3 × 300 MCM 3 × 400 MCM or 4 × 250 MCM
-700A-4
3 × (3×185)
4 × (3×185)
2 × 700 MCM or 3 × 350 MCM 3 × 500 MCM or 4 × 300 MCM
-785A-4
3 × (3×240)
4 × (3×240)
3 × 500 MCM or 4 × 300 MCM 3 × 600 MCM or 4 × 400 MCM
-857A-4
3 × (3×240)
4 × (3×240)
3 × 500 MCM or 4 × 300 MCM 3 × 700 MCM or 4 × 500 MCM
3BFA 01051905 D
Содержание ACQ810-04
Страница 1: ...ABB industry specific drives Hardware manual ACQ810 04 drive modules 200 to 500 kW 300 to 700 hp ...
Страница 4: ......
Страница 10: ...10 ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Planning the cabinet installation ...
Страница 75: ...Installation 75 Assembly drawing frame G1 ...
Страница 76: ...76 Installation Assembly drawing frame G2 ...
Страница 83: ...Installation 83 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Страница 84: ...84 Installation Assembly drawing of installing the drive module to the cabinet frame G1 ...
Страница 85: ...Installation 85 Assembly drawing of installing the drive module to the cabinet frame G2 ...
Страница 89: ...Installation 89 3AUA0000038989 TXD transmitter RXD receiver JRIB V2 V1 V7 V6 1 2 APOW 2 JINT 3 JRIB 1 4 4 JGDR ...
Страница 100: ...100 Installation ...
Страница 104: ...104 Installation checklist ...
Страница 106: ...106 Start up ...
Страница 108: ...108 Fault tracing ...
Страница 128: ...128 Technical data ...
Страница 130: ...130 Dimension drawings Frame G1 Drive module dimensions ...
Страница 131: ...Dimension drawings 131 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Страница 132: ...132 Dimension drawings ...
Страница 133: ...Dimension drawings 133 Frame G1 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Страница 134: ...134 Dimension drawings Frame G2 Drive module dimensions ...
Страница 135: ...Dimension drawings 135 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Страница 136: ...136 Dimension drawings ...
Страница 137: ...Dimension drawings 137 Frame G2 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Страница 138: ...138 Dimension drawings Bottom plate ...
Страница 142: ...142 du dt filters ...
Страница 144: ...3AUA0000120538 Rev A EN 2012 06 27 Contact us www abb com drives www abb com drivespartners ...