requirement of the motor cable shield of the drive is shown below. It consists of
a concentric layer of copper wires with an open helix of copper tape or copper
wire. The better and tighter the shield, the lower the emission level and bearing
currents.
1
3
4
5
2
Insulation jacket
1
Helix of copper tape or copper wire
2
Copper wire shield
3
Inner insulation
4
Cable core
5
Grounding requirements
This section gives general requirements for grounding the drive. When you plan
the grounding of the drive, obey all the applicable national and local regulations.
The conductivity of the protective earth conductor(s) must be sufficient.
Unless local wiring regulations state otherwise, the cross-sectional area of the
protective earth conductor must agree with the conditions that require automatic
disconnection of the supply required in 411.3.2 of IEC 60364-4-41:2005 and be
capable of withstanding the prospective fault current during the disconnection
time of the protective device. The cross-sectional area of the protective earth
conductor must be selected from the table below or calculated according to 543.1
of IEC 60364-5-54.
This table shows the minimum cross-sectional area of the protective earth
conductor related to the phase conductor size according to IEC/UL 61800-5-1
when the phase conductor(s) and the protective earth conductor are made of the
same metal. If this is not so, the cross-sectional area of the protective earth
72 Guidelines for planning the electrical installation
Содержание ACH580-31
Страница 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 30: ...30 ...
Страница 39: ...Operation principle 39 ...
Страница 56: ...56 ...
Страница 90: ...90 ...
Страница 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Страница 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Страница 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Страница 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Страница 131: ...R6 Electrical installation North America NEC 131 ...
Страница 150: ...150 ...
Страница 152: ...152 ...
Страница 166: ... Fan arrow must point up 166 Maintenance ...
Страница 189: ... Package dimensions and weights R6 R3 R8 26 61 11 38 16 65 23 54 25 74 39 06 15 75 45 59 19 76 Technical data 189 ...
Страница 212: ...212 ...
Страница 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Страница 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Страница 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Страница 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Страница 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Страница 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Страница 220: ...220 ...
Страница 242: ...242 ...
Страница 250: ...250 ...
Страница 254: ...254 ...
Страница 261: ...Dimension drawings The dimensions are in millimeters CAIO 01 bipolar analog I O adapter module 261 ...
Страница 262: ...262 ...
Страница 268: ...268 ...
Страница 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Страница 276: ...276 ...
Страница 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...