Safety
WARNING!
Frames R6 and R8: Lift the drive with a lifting device. Use the lifting eyes of
the drive. Do not tilt the drive. The drive is heavy and its center of gravity
is high. An overturning drive can cause physical injury.
Examining the installation site
Examine the installation site. Make sure that:
•
The installation site is sufficiently ventilated or cooled to remove heat from
the drive. See the technical data.
•
The ambient conditions of the drive meet the specifications. See the technical
data.
•
The material behind, above and below the drive is non-flammable.
•
The installation surface is as close to vertical as possible and strong enough
to support the drive.
•
There is sufficient free space around the drive for cooling, maintenance, and
operation. See the free space specifications for the drive.
•
Make sure that there are no sources of strong magnetic fields such as
high-current single-core conductors or contactor coils near the drive. A strong
magnetic field can cause interference or inaccuracy in the operation of the
drive.
Installation positions
There are three alternative ways to install the drive:
•
vertically alone. Do not install the drive upside down.
44 Mechanical installation
4
Содержание ACH580-31
Страница 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 30: ...30 ...
Страница 39: ...Operation principle 39 ...
Страница 56: ...56 ...
Страница 90: ...90 ...
Страница 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Страница 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Страница 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Страница 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Страница 131: ...R6 Electrical installation North America NEC 131 ...
Страница 150: ...150 ...
Страница 152: ...152 ...
Страница 166: ... Fan arrow must point up 166 Maintenance ...
Страница 189: ... Package dimensions and weights R6 R3 R8 26 61 11 38 16 65 23 54 25 74 39 06 15 75 45 59 19 76 Technical data 189 ...
Страница 212: ...212 ...
Страница 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Страница 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Страница 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Страница 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Страница 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Страница 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Страница 220: ...220 ...
Страница 242: ...242 ...
Страница 250: ...250 ...
Страница 254: ...254 ...
Страница 261: ...Dimension drawings The dimensions are in millimeters CAIO 01 bipolar analog I O adapter module 261 ...
Страница 262: ...262 ...
Страница 268: ...268 ...
Страница 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Страница 276: ...276 ...
Страница 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...