DANGER - Risk of electric shock. After disconnecting the input power, always
wait for 5 minutes to let the intermediate circuit capacitors discharge before
you start working on the drive, motor or motor cable.
•
The drive is to be used in a heated, indoor controlled environment. The drive
must be installed in clean air according to the enclosure classification. Cooling
air must be clean, free from corrosive materials and electrically conductive
dust.
•
The maximum surrounding air temperature is 40 °C at rated output current.
The output current is derated for 40…50 °C.
Note: For cabinet-built drives, the maximum surrounding air temperature is
40 °C (104 °F).
•
The drive is suitable for use in a circuit capable of delivering not more than
100 kA rms symmetrical amperes, 480 V maximum when protected by the UL
fuses given elsewhere in this chapter. The ampere rating is based on tests
done according to the appropriate UL standard.
•
The cables located within the motor circuit must be rated for at least 75 °C in
UL-compliant installations.
•
The input cable must be protected with fuses or circuit breakers. These
protective devices provide branch circuit protection in accordance with the
national regulations (National Electrical Code (NEC) or Canadian Electrical
Code). Obey also any other applicable local or provincial codes.
•
WARNING!
The opening of the branch-circuit protective device may be an indication
that a fault current has been interrupted. To reduce the risk of fire or
electric shock, current-carrying parts and other components of the device
should be examined and replaced if damaged.
•
The drive provides motor overload protection. For adjustments, see the
firmware manual.
•
The drive overvoltage category according to IEC 60664-1 is III.
•
To maintain the environment integrity of the enclosure, replace the cable
grommets with field-installed industrial conduit hubs or closure plates required
by the enclosure type (or better).
Declarations of conformity
You can find declarations of conformity in PDF format on the Internet at
. For EU and UK declarations of conformity, see
chapter
The Safe torque off function (page 221)
210 Technical data
Содержание ACH580-31
Страница 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 30: ...30 ...
Страница 39: ...Operation principle 39 ...
Страница 56: ...56 ...
Страница 90: ...90 ...
Страница 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Страница 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Страница 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Страница 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Страница 131: ...R6 Electrical installation North America NEC 131 ...
Страница 150: ...150 ...
Страница 152: ...152 ...
Страница 166: ... Fan arrow must point up 166 Maintenance ...
Страница 189: ... Package dimensions and weights R6 R3 R8 26 61 11 38 16 65 23 54 25 74 39 06 15 75 45 59 19 76 Technical data 189 ...
Страница 212: ...212 ...
Страница 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Страница 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Страница 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Страница 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Страница 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Страница 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Страница 220: ...220 ...
Страница 242: ...242 ...
Страница 250: ...250 ...
Страница 254: ...254 ...
Страница 261: ...Dimension drawings The dimensions are in millimeters CAIO 01 bipolar analog I O adapter module 261 ...
Страница 262: ...262 ...
Страница 268: ...268 ...
Страница 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Страница 276: ...276 ...
Страница 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...