WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered using an external 24 V AC supply.
Start-up
■
Setting the parameters
1.
Power up the drive.
2.
If no warning is shown,
•
make sure that the value of both parameters 15.01 Extension module type
and 15.02 Detected extension module is CMOD-01.
If the warning A7AB Extension I/O configuration failure is shown,
•
make sure that the value of parameter 15.02 is CMOD-01.
•
set the parameter 15.01 value to CMOD-01.
You can now see the parameters of the extension module in parameter group
15 I/O extension module.
3.
Set the parameters of the extension module to applicable values.
Examples are given below.
Parameter setting example for relay output
This example shows how make relay output RO4 of the extension module indicate
the reverse direction of rotation of the motor with a one-second delay.
Setting
Parameter
Reverse
15.07 RO4 source
1 s
15.08 RO4 ON delay
1 s
15.09 RO4 OFF delay
Parameter setting example for digital output
This example shows how to make digital output DO1 of the extension module
indicate the reverse direction of rotation of the motor with a one-second delay.
Setting
Parameter
Digital output
15.22 DO1 configuration
Reverse
15.23 DO1 source
1 s
15.24 DO1 ON delay
1 s
15.25 DO1 OFF delay
272 CMOD-01 multifunction extension module (external 24 V AC/DC and digital
I/O)
Содержание ACH580-31
Страница 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 30: ...30 ...
Страница 39: ...Operation principle 39 ...
Страница 56: ...56 ...
Страница 90: ...90 ...
Страница 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Страница 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Страница 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Страница 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Страница 131: ...R6 Electrical installation North America NEC 131 ...
Страница 150: ...150 ...
Страница 152: ...152 ...
Страница 166: ... Fan arrow must point up 166 Maintenance ...
Страница 189: ... Package dimensions and weights R6 R3 R8 26 61 11 38 16 65 23 54 25 74 39 06 15 75 45 59 19 76 Technical data 189 ...
Страница 212: ...212 ...
Страница 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Страница 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Страница 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Страница 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Страница 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Страница 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Страница 220: ...220 ...
Страница 242: ...242 ...
Страница 250: ...250 ...
Страница 254: ...254 ...
Страница 261: ...Dimension drawings The dimensions are in millimeters CAIO 01 bipolar analog I O adapter module 261 ...
Страница 262: ...262 ...
Страница 268: ...268 ...
Страница 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Страница 276: ...276 ...
Страница 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...