(430 V)
2
600 kVA
= 22.19 mohm
Z
k
= z
k
·
U
N
2
S
N
= 0.072
m
·
0.398
ohm
km
= 67.66 mohm
R
c
= 170
m
·
0.082
ohm
km
= 13.94 mohm
X
c
= 170
=
410 V
2
·
(67.66 mohm)
2
+ (22.19 mohm + 13.94 mohm)
2
I
k2-ph
= 2.7 kA
The calculated short-circuit current 2.7 kA is higher than the minimum short-circuit
current of the drive aR fuse type 170M3817 (900 A). -> The 690 V aR fuse (Bussmann
170M3817) can be used.
Fuses (UL)
The UL Listed fuses in this manual are required for branch circuit protection and
required per NEC. The drives are suitable for use on a circuit capable of delivering
not more than 100 kA symmetrical amperes (rms) at 480 V maximum when
protected by the fuses described below.
ABB recommends Class T fuses listed below. Also allowed are UL Listed 248-8
Class J fast acting, time delay, and high speed fuses, 248-4 Class CC fast acting
fuses and 248-17 Class CF fast acting and time delay fuses of the same nominal
voltage and current rating.
Refer to notes below the tables.
UL (one fuse per phase)
Input current
ACH580-
31-…
UL class
Bussmann
type
Voltage rating
Nominal cur-
rent
V
A
A
3-phase
Un = 480 V
T
JJS-15
600
15
7.0
07A6-4
T
JJS-20
600
20
9.0
012A-4
T
JJS-25
600
25
12.0
014A-4
T
JJS-35
600
35
17.0
023A-4
T
JJS-40
600
40
24
027A-4
T
JJS-50
600
50
29
034A-4
T
JJS-60
600
60
34
044A-4
T
JJS-80
600
80
44
052A-4
T
JJS-90
600
90
54
065A-4
T
JJS-110
600
110
66
077A-4
T
JJS-150
600
150
82
096A-4
T
JJS-200
600
200
111
124A-4
182 Technical data
Содержание ACH580-31
Страница 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 30: ...30 ...
Страница 39: ...Operation principle 39 ...
Страница 56: ...56 ...
Страница 90: ...90 ...
Страница 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Страница 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Страница 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Страница 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Страница 131: ...R6 Electrical installation North America NEC 131 ...
Страница 150: ...150 ...
Страница 152: ...152 ...
Страница 166: ... Fan arrow must point up 166 Maintenance ...
Страница 189: ... Package dimensions and weights R6 R3 R8 26 61 11 38 16 65 23 54 25 74 39 06 15 75 45 59 19 76 Technical data 189 ...
Страница 212: ...212 ...
Страница 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Страница 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Страница 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Страница 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Страница 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Страница 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Страница 220: ...220 ...
Страница 242: ...242 ...
Страница 250: ...250 ...
Страница 254: ...254 ...
Страница 261: ...Dimension drawings The dimensions are in millimeters CAIO 01 bipolar analog I O adapter module 261 ...
Страница 262: ...262 ...
Страница 268: ...268 ...
Страница 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Страница 276: ...276 ...
Страница 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...