conductor must be determined in a manner which produces a conductance
equivalent to that which results from the application of this table.
Minimum cross-sectional area of the corres-
ponding protective earth conductor
Sp (mm2)
Cross-sectional area of the phase conduct-
ors
S (mm2)
S
1)
S ≤ 16
16
16 < S ≤ 35
S/2
35 < S
1) For the minimum conductor size in IEC installations, refer to
Additional grounding requirements – IEC
If the protective earth conductor is not part of the input power cable or input
power cable enclosure, the minimum permitted cross-sectional area is:
•
2.5 mm
2
if the conductor is mechanically protected,
or
•
4 mm
2
if the conductor is not mechanically protected. If the equipment is
cord-connected, the protective earth conductor must be the last conductor
to be interrupted if there is a failure in the strain relief mechanism.
■
Additional grounding requirements – IEC
This section gives grounding requirements according to standard IEC/EN 61800-5-1.
Because the normal touch current of the drive is more than 3.5 mA AC or 10 mA DC:
•
the minimum size of the protective earth conductor must comply with the
local safety regulations for high protective earth conductor current equipment,
and
•
you must use one of these connection methods:
1.
a fixed connection and:
•
a protective earth conductor with a minimum cross-sectional area of
10 mm
2
Cu or 16 mm
2
Al (as an alternative when aluminum cables are
permitted),
or
•
a second protective earth conductor of the same cross-sectional area
as the original protective earth conductor,
or
•
a device that automatically disconnects the supply if the protective
earth conductor is damaged.
2.
a connection with an industrial connector according to IEC 60309 and a
minimum protective earth conductor cross-section of 2.5 mm
2
as part of
a multi-conductor power cable. Sufficient strain relief must be provided.
Guidelines for planning the electrical installation 73
Содержание ACH580-31
Страница 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 30: ...30 ...
Страница 39: ...Operation principle 39 ...
Страница 56: ...56 ...
Страница 90: ...90 ...
Страница 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Страница 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Страница 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Страница 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Страница 131: ...R6 Electrical installation North America NEC 131 ...
Страница 150: ...150 ...
Страница 152: ...152 ...
Страница 166: ... Fan arrow must point up 166 Maintenance ...
Страница 189: ... Package dimensions and weights R6 R3 R8 26 61 11 38 16 65 23 54 25 74 39 06 15 75 45 59 19 76 Technical data 189 ...
Страница 212: ...212 ...
Страница 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Страница 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Страница 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Страница 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Страница 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Страница 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Страница 220: ...220 ...
Страница 242: ...242 ...
Страница 250: ...250 ...
Страница 254: ...254 ...
Страница 261: ...Dimension drawings The dimensions are in millimeters CAIO 01 bipolar analog I O adapter module 261 ...
Страница 262: ...262 ...
Страница 268: ...268 ...
Страница 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Страница 276: ...276 ...
Страница 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...