Section 3 Configuration
Controller IP Addresses
3BSE 027 941 R301
95
Controller IP Addresses
Before a redundant hardware installation you have to concider the following.
Setting CPU as Redundant in Control Builder M
The redundant PM861/PM864 must be set as redundant in the Control Builder M
Project Explorer. Also see Hardware Configuration and Redundancy in the
Control Builder M online help.
Remember that the Backup controller IP Addresses must be set in the primary
Processor Unit. This can only be done though the IPConfig tool.
There are three alternatives:
•
Disable interface.
•
Use default rule.
•
Specify an address of your own.
Use Default rule if not in conflict with any other IP-address on the network.
In the case you need to set an IP address to a redundant CPU, the backup CPU needs
to be turned off (powered down). Otherwise the backup CPU takes over and you
will not be connected.
Содержание AC 800M
Страница 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Страница 2: ......
Страница 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Страница 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Страница 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Страница 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Страница 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Страница 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Страница 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Страница 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Страница 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Страница 228: ...QGH 228 3BSE 027 941 R301...
Страница 229: ......