Section 4 Operation
AC 800M Controller (PM8xx)
3BSE 027 941 R301
111
Switches and Push buttons
Connectors
Table 16. PM8xx – Switches and Push buttons
Marking
Type
Function
INIT
Manual Push
button
Initiates
1. Cold Restart if INIT is held less than 2.5
seconds.
2. Controller Reset if INIT is held more than
3 seconds.
If INIT is pushed on the Primary CPU in
redundant configuration a switchover to the
backup CPU will be initiated.
Table 17. PM8xx/TP830 – Connectors
Marking
Function
L+
L–
SA
SB
External Power Supply Connection
+24 V DC supply
0 V
Redundant Power Supply monitoring input
Redundant Power Supply monitoring input
SH
B+
B–
External Battery Connection
Shield (Screw Connector)
Battery Positive (Screw Connector)
Battery Negative (Screw Connector)
Tx
Rx
ModuleBus Connection
Data Transmission Port (Optical)
Data Reception Port (Optical)
Note – Duplex or Simplex optical cables may be used.
Содержание AC 800M
Страница 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Страница 2: ......
Страница 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Страница 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Страница 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Страница 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Страница 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Страница 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Страница 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Страница 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Страница 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Страница 228: ...QGH 228 3BSE 027 941 R301...
Страница 229: ......