Site Selection and Building Requirements
Section 2 Installation
44
3BSE 027 941 R301
When planning a control system installation, the following points must be
considered:
•
Temperature:
–
It is important to note the ambient air temperature as well as that within
enclosures. Lower temperatures increase system reliability and
availability.
–
If maximum permitted temperatures are exceeded, the anticipated lifetime
of wet, electrolytic capacitors and most semiconductors will be greatly
reduced.
•
Vibration:
–
Regarding routine vibration it is recommended that floor
enclosures/cabinets stand on a sound, level surface, and that wall
enclosures/cabinets are mounted on sound, vertical walls.
–
Should the AC 800M system be installed in a control room, adjacent to
large machinery such as shakers or large presses where frequent major
vibration is expected, then shock absorbers or an isolation pad may be
required to protect system equipment. Shock absorbers will normally
protect the equipment from sustained low-level vibrations that are
perceivable, but not unduly excessive.
–
It is recommended that additional fastening screws be used to prevent
vibration-generated noise.
–
If vibrations or shock are a major factor, further consideration must be
given to more extreme measures to reduce the problem.
•
Cooling:
–
Cooling the electronics is achieved by self-convection. The AC 800M
units are designed for wall mounting and must be mounted horizontally
onto a DIN-rail to avoid generating high temperatures within the units.
–
ABB cabinets (RM550 or RE820) may be used up to an ambient
temperature of 40 °C (104 °F), with no requirement for additional cooling
equipment, such as fans.
Содержание AC 800M
Страница 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Страница 2: ......
Страница 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Страница 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Страница 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Страница 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Страница 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Страница 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Страница 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Страница 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Страница 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Страница 228: ...QGH 228 3BSE 027 941 R301...
Страница 229: ......