SECURITY AND ARMING
Setting
Default
Description
Allow Master Code to Access
Security and Arming
Disabled
Allow the master code to access these features and settings.
NOTE:
this option shall be disabled for UL/cUL. This option shall be enabled for UL Commercial Burg
installations.
Normal Entry Delay
30 Secs
How much time users have to enter their code after opening a door (30-240secs). With SIA limits disabled
the minimum time can be set to 5 secs.
NOTE:
For UL Commercial Burg (UL1610) maximum entry delay should not exceed 60s
Normal Exit Delay
60 Secs
How much time users have to exit the location before the panel arms itself (30-254secs). With SIA limits
disabled the minimum time can be set to 5 secs. Door/Window group 10 follows the “Normal Exit Delay”
NOTE:
For UL Commercial Burg (UL1610) maximum exit delay should not exceed 60s
Long Entry Delay
100 Secs
A second separate entry delay that can be used on a sensor needing more time when tripped (45-240secs).
With SIA limits disabled the minimum time can be set to 5 secs
Long Exit Delay
120 Secs
A second separate exit delay that can be used on a sensor needing more time when tripped (45-254secs).
With SIA limits disabled the minimum time can be set to 5 secs. Door/Window group 12 follows the “Long
Exit Delay”
QOLSYS CONFIDENTIAL AND PROPRIETARY
PAGE OF
41
177
PROGRAMMING
Содержание Qolsys IQ Panel 2
Страница 8: ...INSTALLING THE PANEL...
Страница 13: ...USER INTERFACE...
Страница 17: ...PROGRAMMING...
Страница 52: ...SECURITY SENSORS...
Страница 84: ...WI FI DEVICES...
Страница 91: ...Z WAVE DEVICES...
Страница 102: ...BLUETOOTH DEVICES...
Страница 110: ...SYSTEM TESTS...
Страница 135: ...CUSTOMIZATION...
Страница 148: ...MAINTENANCE...
Страница 154: ...TROUBLESHOOTING...
Страница 164: ...LEGAL...
Страница 172: ...SPECIFICATIONS...