Installation of Preset Level Sensor Holder
Side Wall
Mount
Figure 5
Discharge Pipe
Mount
Page 3 of 9
Operation and Maintenance Manual
7000 Apple Tree Avenue, Bergen, NY 14416 Phone: (800) 543-2550-Fax: (585) 494-1839-www.libertypumps.com
Pump
Start
High Level
Probe
High Level
Float
Circuit Board
Figure 6
Figure 4
DWG#7235000I
Manual 7235000I
Off
Probe
Operation and Maintenance Manual
Operation and Maintenance Manual
1. Review figures 4, 5 and 6.
2. Attach sensor holder to discharge pipe or separate pipe (mounted to side wall) using the stainless
steel pipe clamp. Make sure sensor is clear of inlet water and at least 2 inches away from any conductive
material. Make sure the bottom probe (off level) is at the same height as the top of the pump or just slightly
below ensuring submergence of the pump. See figure 5.
3. Route the five conductor cable to the control panel through the liquid tight cord connector and tighten
compression nut.
4. Connect the wires from the level sensor to the terminal strip inside the control panel. See figure 6.
5. If splicing on sensor cable is required:
A. For any splicing longer than 100 feet, consult factory.
B. Use liquid tight junction boxes and appropriate liquid tight
connectors and/or conduit.
C. Do not mix high & low voltage circuits in same junction box or conduit
D. For level sensor splice, it is recommended to use 3 pair-twisted
22 AWG shielded cable.
Preset Level
Sensor Holder
Off
Probe
Start
Probe
Alarm
Probe
Float Float
Green
Y
ellow
Red
White
Black
Sheild
Common
Oil
Water
Auxiliary Contacts
24 VAC/VDC
100 mA Max
Conect to Remote Alarm
Or BAS/SCADA System
Class 2 Low Voltage.
Caution! Do Not Run In Same Conduit
As High Voltage Circuits