7000 Apple Tree Avenue Bergen, NY 14416 Phone: (800) 543-2550-Fax: (585) 494-1839-www.libertypumps.com
Operation and Maintenance Manual
Page 9 of 9
DWG#7235000I
Manual 7235000I
:
Operation and Maintenance Manual
Operation and Maintenance Manual
Operation and Maintenance Manual
Maintenance
1. The preset level control must be kept clean and free of rust, mud, soap or any conductive material.
2. Every year clean probes keeping them free of debris, calcium or iron deposits.
3. Fuses in control panel are 5mm X 20mm 1 amp for F1
(Spare fuses are included for your convenience)
4. Every year replace 9 Volt Battery in Remote Alarm.
Trouble Shooting
Symptom
Possible
Cause Action
Pump does not run
Panel Power Cord Unplugged
Plug in Outlet, Check Power
Pump not plugged into panel
Plug pump to panel plug
Defective
Contactor
Replace
Contactor
Loose
level
sensor
wires Tighten
connections
Pump
failure
Replace
pump
Pump turns off before
Poor pump ground or system ground Check grounding system
bottom probe
Pump Runs Continuously
Make Sure the Preset Level Sensor cable and the power cord from
the pump are separated by at least 2” in the tank and 2” apart running
into
the
control
panel.
Summary of Contents for Aquaflush Z6000
Page 3: ...P 1A AND P 1B WATER CLOSET ...
Page 17: ...P 2 AND P 2B URINAL ...
Page 31: ...P 3 LAVATORY ...
Page 36: ...P 5 KITCHEN SINK ...
Page 42: ...EWC 1 EWC 2 WATER COOLER ...
Page 56: ...WH 1 WATER HEATER ...
Page 77: ...HWC 1 RECIRC PUMP ...
Page 80: ...SP 1 SUMP PUMP ...