DESCRIPTION

The Zonex Systems 

RMOD

is a microprocessor based digital communi-

cating HVAC Relay Module for the 

ZonexCommander (Plus)

system. The

RMOD

controls Gas/Electric 2-stage heat and cool, as well as Heat Pump,

2-stage cool and 3-stage heat, based on supply air temperature. The

RMOD

provides high and low limits to protect HVAC system components.

Each 

RMOD

can communicate with up to 20 thermostats. There can

be up to 4 

RMOD

controllers per Command Center; however, each

Command Center controls up to 20 thermostats. The total number of
thermostats cannot exceed 20 on each Command Center.

The 

RMOD

and corresponding 

ModStats

must be configured into the

ZonexCommander (Plus)

system before the 

RMODs

will communicate.

See Installation Guide.

INSTALLATION

RMOD circuit board 

The 

RMOD

can be installed with the Command Center or in the HVAC unit

it is controlling. It must be protected from the elements in an area
where the temperature range is from 25° to 125° non-condensing. DO
NOT install the Command Centers or 

RMODs

in close proximity to large

transformers, VFDs, or any device that produces electrical energy fields.

1. Install the 

RMOD

where it can be properly accessed.

3. The 

RMOD

is shipped from the factory to operate in the Gas Electric

mode. For Heat Pump operation, place the HP jumper tab over
both pins.

4. For Heat Pump “O” reversing valve operation the O/B jumper tab is

on one pin. For reversing valve “B” operation, place the jumper tab
over both pins.

intermittent fan. For Constant FAN in the Occupied mode, place the
jumper tab over the middle and upper pins (ON).

of the bypass

take-off.

bypass take-off (Gas Electric), or between the indoor coil and strip
heat elements (Heat Pump AHU).

Addressing & Calibration

button until the correct address appears, and release.

2. Energize the FAN only and check 

RMOD

display calibration.

adjust calibration.

4. Return air temperature is displayed when the UP and DN buttons are

holding down these buttons.

Wiring

8740).

any other ac voltage wiring; it must be run completely separate. Use

switch to the EM terminals on the 

RMOD

.

The 

RMOD

is ready to be configured in the

ZonexCommander (Plus)

program.
See Installation Guide.

RMOD UNIT DESCRIPTION / INSTALLATION

HVAC UNIT CONTROLLER

Sensors – Supply and Return (LAT)

2. Install the LV AIR sensor (

LAT

) in the supply duct ahead of the

1. Install the RA sensor (

LAT

) in the return duct, ahead

RMOD

to ON from S1, and press the 

ADR

 button. To change the

address from 92, continue to hold the 

ADR

 button; and press the UP

1.  Set the address for the 

RMOD

(92, 93, 94 or 95) by switching the

5. Set the FAN jumper tab (JPR1) on the center and lower pin (AUTO) for

2.

The 

RMOD

 is powered by the Command Center transformer

by daisy chaining the 24vac from Command Center to the 

RMOD

.

You will need to properly size the transformer to the total number

of dampers on the system.

with 18 AWG thermostat wire.

3. When the sensor leads are too short, you may extend the wire

3.  Constant display indicates supply air temperature. Rotate R52 to

pressed simultaneously. Rotate R45 to adjust the calibration, while

4. Connect the 

RMOD

outputs to the HVAC system.

5. If Emergency Heat is to be controlled by a remote switch, wire a SPST

3. Connect the Supply Air sensor to the LV Air terminal screw block.

2. Connect the Return Air sensor to the RA terminal screw block.

NOTE: The twisted pair communication wire cannot be installed with

1.  Connect the twisted pair communication wires to RX and TX (Belden

shielded twisted pair (Belden 8450) if there is any potential

for electrical interference.

Summary of Contents for ZonexCommander

Page 1: ...1 Installation and Applications Manual Part ZCMAN ZonexCommander ZonexCommander Plus Network All Your HVAC Equipment Centralized DDC Communications for Stand Alone HVAC and Zoned Systems Rev Oct 2014...

Page 2: ...view 16 Sequence Of Operation 17 18 Command Center ZonexCommander Plus 19 Installation Instructions 20 ModStat Thermostat and Supplemental Heat Applications 21 22 Sequence Of Operation 23 RMOD Termina...

Page 3: ...Zonex is designed to network one or multiple zoned units on one two wire twisted pair for remote communications over the Internet in buildings too large for multiple programmable thermostats but too...

Page 4: ...provide expansion capability to to 20 devices ModStat MODS2 DIGICOM thermostats and for multiple zoned HVAC systems Each Command Center supports up For use with ZonexCommander Plus systems only capac...

Page 5: ...pumps blowers lighting etc The devices to be cycled ON and OFF by programmed schedules in the Commander software Status is displayed on the REVIEW screen for dedicated address from 01 to 20 The load a...

Page 6: ...es are controlled with a relay device RLYCOM Each of these devices can be scheduled through the simple Windows based ZonexCommander software and communicate to the Command Center via a daisy chained 2...

Page 7: ...oftops or split systems COMMUNICATING ACCESSORIES Optional STAND ALONE EQUIPMENT COMMAND CENTER 21 to 80 additional 20 Thermostats Stand Alone Equipment SENDCOM Duct Temperature Sensor 1 per HVAC unit...

Page 8: ...hen Emergency Heat is selected Y1 and Y2 are de energized and W2 and G are energized When the DIGIHP thermostat is configured for O reversing valve on an active heat call the O B output will be de ene...

Page 9: ...strips or solder NOTE for systems with potential electrical interference such as large transformers VFDs etc shielded twisted pair Belden 8450 may be used for the communications loop ZONEXCOMMANDER IN...

Page 10: ...t side terminal block is for the RX TX communication circuits There are two sets of RX TX terminals on the base to make daisy chain wiring from device to device straightforward and simple 1 Use minimu...

Page 11: ...cool call when the space temperature rises 1 above the cool setpoint Y2 will energize when the space temperature rises 2 above the cool setpoint When the room temperature is less than 2 from setpoint...

Page 12: ...RY SENSOR CALIBRATION R12 OUTSIDE AIR OA POWER LED INDICATOR MAIN CONTROL CHIP ZONEXCOMMANDER USB COMPUTER COMMUNICATION RS 485 TWISTED PAIR POLARITY SENSITIVE BELDEN 8740 OUTDOOR AIR SENSOR TERMINAL...

Page 13: ...13 ZONEXCOMMANDER WIRING OVERVIEW ROOFTOP UNITS UP TO 20 PER COMMAND CENTER...

Page 14: ...dampers based on zone demand The ZonexCommander Plus system can be applied to existing HVAC systems or new installations providing central control of HVAC operations using Windows based ZonexCommande...

Page 15: ...15 ZONEXCOMMANDER PLUS COMPONENT SELECTION GUIDE...

Page 16: ...o be cycled The W1 output signal is connected to the heating device input terminal and the coil of the fan relay This is required for electric heat and gas furnaces with no fan control See Fig 2 on a...

Page 17: ...ommunicate a heat mode call to the is two degrees or more below room temperature ModStat will modulate the damper to 100 open If the room temperature is within two degrees of setpoint the ModStat will...

Page 18: ...Release button 1 Push UP button until display shows H 2 Current setpoint will be displayed 3 Push UP or DN button until desired setpoint is displayed 4 Release button operation A shorted sensor or wir...

Page 19: ...SENSOR CALIBRATION R12 OUTSIDE AIR POWER LED INDICATOR MAIN CONTROL CHIP ZONEX COMMANDER PLUS COMMUNICATION RS 485 TWISTED PAIR POLARITY SENSITIVE BELDEN 8740 SENSOR TERMINAL OA OUTSIDE AIR ONLY TERMI...

Page 20: ...X Wire nuts are never to be used on the communication wire When making connections use screw type terminal strips or solder NOTE for systems with potential electrical interference such as large transf...

Page 21: ...After setting the address the thermostat will automatically go back to normal operation and the setpoint temperature will replace the address number just programmed Manual Operation Adjusting Setpoint...

Page 22: ...hen the space temperaturemeetstheheatsetpoint When configured for Reheat if the space temperature drops 1 below modulate the damper open The heat call will terminate when the space system goes into th...

Page 23: ...t and 75 F cool as measured by the MIX Air sensor in the return air TEMPERATURE LIMITS AND STAGING The RMOD monitors the leaving air temperature for staging and Hi Low 145 F Staging is based on the li...

Page 24: ...NSTALLED STATUS LEDs PWR1 Y1 Y2 W1 and O B W2 G 3 4 5 6 7 8 10 9 11 TERMINAL DESIGNATIONS TX Data transmit RX Data receive RA Return air sensor Gas Electric G Fan output W2 Stage 2 heat output W1 Stag...

Page 25: ...heat elements Heat Pump AHU Addressing Calibration button until the correct address appears and release 2 Energize the FAN only and check RMOD display calibration adjust calibration 4 Return air temp...

Page 26: ...26 RMOD WIRING OVERVIEW All RX communication wires must be connected to the RX terminals All TX communication wires must be connected to the TX terminals The RX and TX wires should never intersect...

Page 27: ...sensor controls low and high temperature limits and heat cool staging RA return air sensor controls unit operation in communication failure mode Keep sensor wires and power wires separate NOTE Shorte...

Page 28: ...gh the 1 4 hole 5 Attach the SENDCOM assembly to the duct or plenum with the sheet metal screws provided 6 Locate the position in the return duct or plenum for the return sensor and drill a 1 4 hole s...

Page 29: ...will be seen on address 1 2 3 and 4 current room temperatures On ZonexCommander Plus systems a SENDCOM cannot be addressed for thermostats 1 2 3 or 4 so start addressing any stand alone equipment in a...

Page 30: ...TION When the RLYCOM is in the Occupied mode the on board relays are energized In the Unoccupied mode the relays are de energized The mode status is displayed on the REVIEW screen of the Commander pro...

Page 31: ...hart 0 1 friction loss per 100 of duct All CFMs listed are approximate For accurate selection use duct sizing table or device MEDIUM PRESSURE STMPD MODSTAT L D W SIZE 6 8 10 12 14 16 6 8 10 12 14 16 D...

Page 32: ...r drive time open and close is 90 seconds RECTANGULAR MEDIUM PRESSURE ZONE DAMPERS Zonex Systems rectangular medium pressure dampers are recommended for systems under 7 5 tons with a maximum different...

Page 33: ...that modulates up and down to control air and throw remain constant This keeps the air hugging the ceiling which maximizes room air mixing and minimizes the waterfall effect ZONE DAMPERS RECTANGULAR D...

Page 34: ...n should be applied to the round pipe and be butted against the hat section do not insulate the motor The motor generates enough heat so that no condensation will develop on it 5 Remember to allow a 1...

Page 35: ...undersize the bypass damper ROUND BYPASS DAMPER SELECTION The Zonex Systems STMPD damper is used for round bypass applications When you know the bypass CFM requirements use the ROUND BYPASS SELECTION...

Page 36: ...2000 13333 14667 16000 36 9000 10500 12000 13500 15000 16500 18000 40 10000 11667 13333 15000 16667 18333 20000 44 11000 12833 14667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 2400...

Page 37: ...ol IPC and air 3 Do not install the bypass damper outside dedicated 24vac 40VA transformer 2 Bypass damper and controller are powered by a recommended for 100 of system CFM system and not undersized B...

Page 38: ...ve Y outputs to unit on the zone control board and to Note 1 To open all dampers it may be necessary to translates to inches of W C one next to the potentiometer The Voltage reading the leads on the C...

Page 39: ...CD into the computer drive and note which drive is being used 2 Click on My Computer 1 Place Systems Software Master CD in the CD drive Installing System Software 4 Under the General Tab for propertie...

Page 40: ...events for each thermostat and RLYCOM Zoned Units Tab Used only with ZonexCommander Plus allocates thermostats to their respective units when multiple units are included in the system SYSTEM START UP...

Page 41: ...store the password NOTE Your password should be retained elsewhere If it is lost the program will have to be re installed and all information re entered Adding Modifying or Deleting Records To add or...

Page 42: ...ord to be deleted f Click on Records g Click on Delete h Click on File then click on Save i Click on Exit to return to the WELCOME Tab Connecting to the Zonex System 1 Click on the Connect Now button...

Page 43: ...nd Settings to place this information into memory Date Time will appear on the upper right of the screen 2 Click on the right or left arrow next to the month and year to select the current month or cl...

Page 44: ...by returning to the REVIEW Tab If the thermostat number you selected is Red it is locked if it is Black it is unlocked If necessary repeat the sequence above to change to desired setting Reviewing Sys...

Page 45: ...setting 6 SENDCOM communications are used to display RA SA temperatures from stand alone units a Place the cursor directly over a Current Room Temperature thermostat number with a SENDCOM attached an...

Page 46: ...isplay thermostat address numbers and names and click on an address b After selecting the desired address the current Occupied and Unoccupied temperature setpoints for that thermostat will be 4 After...

Page 47: ...y a Select the thermostat or RLYCOM address from the pull down menu under Select Thermostat b Click on the radio button next to the day of the week to be scheduled Schedule each day individually After...

Page 48: ...he thermostat address numbers to be assigned to that RMOD one or more addresses may be highlighted NOTE When DIGICOM DIGIHP thermostats or RLYCOM devices are part of the installation they must be addr...

Page 49: ...nex Systems 6 After the logging commences you may minimize the Zonex program in order to use other computer functions but do not turn off the computer or trending program during data collection This w...

Page 50: ...ge to return to Page 1 of the Trending program Then select another thermostat you wish to analyze by using the drop down arrow and the data will be retrieved quickly 13 After the data is collected if...

Page 51: ...thermostat address add 70 B Verify device has the correct address For A Verify device is powered up 1 SENDCOM reporting 0 on Read Sensors window SENDCOM Common Ground Phasing E Check polarity of R C...

Page 52: ...00 228 2966 M F 6 30 AM 5 00 PM PST DAY OCC DAY UNOCC NIGHT OCC NIGHT UNOCC DAY ADR NAME H C H C H C H C MON TUES WED THUR FRI SAT SUN MON TUES WED THUR FRI SAT SUN MON TUES WED THUR FRI SAT SUN MON T...

Page 53: ......

Page 54: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations Part ZCMAN ZonexCommander Plus Network All Your HVAC Equipment Centralized DDC Communication...

Reviews: