33
6”
Neck Vel
400
500
600
700
800
900
Δ
P
0.011
0.016
0.023
0.035
0.04
0.055
CFM
80
98
120
135
157
176
Throw 50 FPM
4’
4’
5’
6’
6’
7’
8”
Neck
400
500
600
700
800
900
Δ
P
0.019
0.03
0.045
0.056
0.041
0.093
CFM
140
170
207
247
280
315
Throw 50 FPM
5’
6’
7’
8’
9’
10’
10”
Neck Vel
400
500
600
700
800
900
Δ
P
0.029
0.045
0.066
0.09
0.12
0.146
CFM
218
273
330
382
438
497
Throw 50 FPM
6’
8’
9’
10’
11’
12’
12”
12”
2”
24”
COLLAR:
PLACE ON SIDE
OR TOP
D-FUSER ZONE DAMPER
Zonex Systems
D-Fuser is a combination zone damper and diffuser. It
mounts in a standard 2’ x 2’ T-bar ceiling opening, providing for simple
installation and easy maintenance access. The D-Fuser is a cone shaped
fluidic nozzle with a platen that modulates up and down to control air
and throw remain constant. This keeps the air hugging the ceiling
which maximizes room air mixing and minimizes the “waterfall” effect.
ZONE DAMPERS
RECTANGULAR DAMPER CAPACITIES*
Dampers listed below are standard sizes. For larger sizes and capacities contact the factory.
*
These air quantities were derived from a duct sizing chart .1” friction loss per 100’ of duct. All CFMs listed are approximate. For accurate selection
use duct sizing table or device.
AT NECK VELOCITIES UP TO 700 FPM
NC LESS THAN 30
flow. As the platen moves up, the air volume is reduced but the air velocity
The D-Fuser is a fully modulating power open, power close damper
using a 24vac 60Hz 2 VA motor. Motor drive time from full open to
full close is 90 seconds. The D-Fuser connects to round duct either on
the side or top. Collars are available for 6", 7", 8", 9" and 10" duct.