5
ZONEX COMPONENT DESCRIPTIONS
Commander
software and have a manual two-hour override. When
the thermostats are “locked,” the setpoints can be adjusted locally by
The Heat / Cool setpoints and address assignments are stored in
non-volatile memory to insure recovery in the event of a power inter-
ruption. Thermostats are powered with 24vac, and communication is
through the RS-485 twisted pair (Belden 8740) communication wire.
COMMUNICATION WIRE SPECIFICATION RS-485
The
Commander
System sends and receives data from the Command
Center to all communicating devices through a 2-conductor twisted pair
RS-485 link (Belden 8740). The communication wire has a maximum
run length of 4,000 L Ft. The communication link is a vital component
of any DDC system, and it must be installed correctly using the correct
wire for the specific application.
For standard applications the basic twisted pair (Belden 8740) wire is
used, which is daisy chained to each communicating device. For
installations with any potential for electrical interference such as caused
shielded twisted pair (Belden 8450) should be used to insure clean
communications.
OLAT - 5vdc OUTSIDE AIR SENSOR
The LAT Thermistor sensor assembly is provided with the
Zonex-
Commander
and
ZonexCommander (Plus)
Command Centers to
provide the Outside Air Temperature which is displayed on the System
screen of the
ZonexCommander/Commander (Plus)
program.
COMPUTER SPECIFICATIONS
A dedicated on-site “control” computer is
not required
. All of the
ZonexCommander
Family of control systems are accessed by Windows
OPTIONAL DEVICES
SENDCOM Sensor
The
SENDCOM
is a microprocessor
based communicating air duct
device is used to display Supply and
requires a
SENDCOM
to display
Return and Supply air temperature for
that particular system. This data is
transmitted to and displayed on the
Commander
software.
The
SENDCOM
is designed for installation on the supply duct, with a
remote sensor for the return duct. The
SENDCOM
does not use a
dedicated address on the communication link; it piggybacks a
thermostat address and displays data when that thermostat number
temperature.
device equipped with two SPDT relays,
which are used for controlling fans,
pumps, blowers, lighting, etc. The
devices to be cycled ON and OFF
by programmed schedules in the
Commander
software. Status is
displayed on the REVIEW screen for
dedicated address from 01 to 20. The load applied to the relay
mode and de-energize in the Unoccupied mode.
TCIP Network Device
LAT – 5vdc TEMPERATURE SENSORS
no more than 2° above or below the locked setpoints.
setpoints, system status, override and thermostat address.
The Zonex thermostats are microprocessor
control zone dampers.
(2-position) are zone thermostats, which
The
ModStat
(modulating) and
MODS2
System through the Internet or Ethernet Network using an assigned
IP address and Port Forwarding.
The Network device includes
installation software and the
Commander
Network version
operating software.
The factory set Heat and Cool setpoints are 70° and 75°, and the factory
set address is 25. Thermostats can be electronically "locked" by the
the iServer with power supply,
Communicating Supply and Return Air Temperature Sensors
RLYCOM
The
RLYCOM
is a communicating
RLYCOM
enables these auxiliary
verification. Each
RLYCOM
uses a
contacts must not exceed one amp at 24vac. The
RLYCOM
is designed
based, auto changeover, digital commu-
nicating thermostats. The thermostats
have a large, easy-to-read LCD display
with a distinctive grey backlight. The
display is designed to clearly indicate
by large transformers, VFDs, ballasts and other electrical devices,
LAT
sensors are used on the
RMOD
and
SENDCOM
devices
for Return and Supply Air temperature sensing. The Supply
and Return sensors provide data to the
RMOD
and
ModCC /
CMod
for proper system capacity control and HI/LO limiting. The
SENDCOM
has a supply sensor, which is factory installed in the
sensor is included for field installation on the return plenum.
enclosure for supply plenum installation; and the remote return
The TCIP device provides communication with the
Commander
operating systems. Our systems can be easily accessed with a direct
connected computer or the optional TCIP device for Internet or
Ethernet access.
temperature sensor. This optional
Return air on stand-alone HVAC
systems. Each stand-alone HVAC system
is selected by double clicking over that thermostat's current room
to switch 24vac circuits only. The relays energize in the Occupied
based Laptop or Desktop computers using Windows 7, 8,XP or Vista
space temperature from 57° to 92°, heat and cool