ZONEX COMPONENT DESCRIPTIONS

Commander

software and have a manual two-hour override. When

the thermostats are “locked,” the setpoints can be adjusted locally by

The Heat / Cool setpoints and address assignments are stored in
non-volatile memory to insure recovery in the event of a power inter-

ruption. Thermostats are powered with 24vac, and communication is
through the RS-485 twisted pair (Belden 8740) communication wire.

COMMUNICATION WIRE SPECIFICATION RS-485

The 

Commander

System sends and receives data from the Command

Center to all communicating devices through a 2-conductor twisted pair
RS-485 link (Belden 8740). The communication wire has a maximum
run length of 4,000 L Ft. The communication link is a vital component
of any DDC system, and it must be installed correctly using the correct
wire for the specific application.

For standard applications the basic twisted pair (Belden 8740) wire is
used, which is daisy chained to each communicating device. For
installations with any potential for electrical interference such as caused

shielded twisted pair (Belden 8450) should be used to insure clean
communications.

OLAT - 5vdc OUTSIDE AIR SENSOR

The LAT Thermistor sensor assembly is provided with the 

Zonex-

Commander

and 

ZonexCommander (Plus)

Command Centers to

provide the Outside Air Temperature which is displayed on the System
screen of the 

ZonexCommander/Commander (Plus)

program.

COMPUTER SPECIFICATIONS

A dedicated on-site “control” computer is 

not required

.  All of the

ZonexCommander

Family of control systems are accessed by Windows

OPTIONAL DEVICES

SENDCOM Sensor 

The 

SENDCOM

is a microprocessor

based communicating air duct

device is used to display Supply and

requires a 

SENDCOM

to display

Return and Supply air temperature for
that particular system. This data is
transmitted to and displayed on the

Commander

software.

The 

SENDCOM

is designed for installation on the supply duct, with a

remote sensor for the return duct. The 

SENDCOM

does not use a

dedicated address on the communication link; it piggybacks a
thermostat address and displays data when that thermostat number

temperature.

device equipped with two SPDT relays,
which are used for controlling fans,
pumps, blowers, lighting, etc.  The

devices to be cycled ON and OFF
by programmed schedules in the

Commander

software. Status is

displayed on the REVIEW screen for

dedicated address from 01 to 20.  The load applied to the relay

mode and de-energize in the Unoccupied mode.

TCIP Network Device

LAT – 5vdc TEMPERATURE SENSORS

no more than 2° above or below the locked setpoints.

setpoints, system status, override and thermostat address.

The Zonex thermostats are microprocessor

control zone dampers.

(2-position) are zone thermostats, which

The 

ModStat

(modulating) and 

MODS2

System through the Internet or Ethernet Network using an assigned

 IP address and Port Forwarding.

The Network device includes 

installation software and the

Commander

 Network version

operating software.

The factory set Heat and Cool setpoints are 70° and 75°, and the factory
set address is 25. Thermostats can be electronically "locked" by the

the iServer with power supply, 

Communicating Supply and Return Air Temperature Sensors

RLYCOM 

The 

RLYCOM

is a communicating

RLYCOM

 enables these auxiliary

verification. Each 

RLYCOM

uses a

contacts must not exceed one amp at 24vac. The 

RLYCOM

is designed

based, auto changeover, digital commu-
nicating thermostats.   The thermostats

have a large, easy-to-read LCD display 
with a distinctive grey backlight.  The 
display is designed to clearly indicate

by large transformers, VFDs, ballasts and other electrical devices,

LAT

  sensors are used on the 

RMOD

 and 

SENDCOM

 devices

for Return and Supply Air temperature sensing.  The Supply

and Return sensors provide data to the 

RMOD

and 

ModCC /

CMod

for proper system capacity control and HI/LO limiting.  The

SENDCOM

has a supply sensor, which is factory installed in the

sensor is included for field installation on the return plenum.

enclosure for supply plenum installation; and the remote return

The TCIP device provides communication with the 

Commander

operating systems. Our systems can be easily accessed with a direct
connected computer or  the optional TCIP device for Internet or
Ethernet access.

temperature sensor. This optional

Return air on stand-alone HVAC
systems. Each stand-alone HVAC system 

is selected by double clicking over that thermostat's  current room

to switch 24vac circuits only. The  relays energize in the Occupied

based Laptop or Desktop computers using Windows 7, 8,XP or Vista

space temperature from 57° to 92°, heat and cool

Summary of Contents for ZonexCommander

Page 1: ...1 Installation and Applications Manual Part ZCMAN ZonexCommander ZonexCommander Plus Network All Your HVAC Equipment Centralized DDC Communications for Stand Alone HVAC and Zoned Systems Rev Oct 2014...

Page 2: ...view 16 Sequence Of Operation 17 18 Command Center ZonexCommander Plus 19 Installation Instructions 20 ModStat Thermostat and Supplemental Heat Applications 21 22 Sequence Of Operation 23 RMOD Termina...

Page 3: ...Zonex is designed to network one or multiple zoned units on one two wire twisted pair for remote communications over the Internet in buildings too large for multiple programmable thermostats but too...

Page 4: ...provide expansion capability to to 20 devices ModStat MODS2 DIGICOM thermostats and for multiple zoned HVAC systems Each Command Center supports up For use with ZonexCommander Plus systems only capac...

Page 5: ...pumps blowers lighting etc The devices to be cycled ON and OFF by programmed schedules in the Commander software Status is displayed on the REVIEW screen for dedicated address from 01 to 20 The load a...

Page 6: ...es are controlled with a relay device RLYCOM Each of these devices can be scheduled through the simple Windows based ZonexCommander software and communicate to the Command Center via a daisy chained 2...

Page 7: ...oftops or split systems COMMUNICATING ACCESSORIES Optional STAND ALONE EQUIPMENT COMMAND CENTER 21 to 80 additional 20 Thermostats Stand Alone Equipment SENDCOM Duct Temperature Sensor 1 per HVAC unit...

Page 8: ...hen Emergency Heat is selected Y1 and Y2 are de energized and W2 and G are energized When the DIGIHP thermostat is configured for O reversing valve on an active heat call the O B output will be de ene...

Page 9: ...strips or solder NOTE for systems with potential electrical interference such as large transformers VFDs etc shielded twisted pair Belden 8450 may be used for the communications loop ZONEXCOMMANDER IN...

Page 10: ...t side terminal block is for the RX TX communication circuits There are two sets of RX TX terminals on the base to make daisy chain wiring from device to device straightforward and simple 1 Use minimu...

Page 11: ...cool call when the space temperature rises 1 above the cool setpoint Y2 will energize when the space temperature rises 2 above the cool setpoint When the room temperature is less than 2 from setpoint...

Page 12: ...RY SENSOR CALIBRATION R12 OUTSIDE AIR OA POWER LED INDICATOR MAIN CONTROL CHIP ZONEXCOMMANDER USB COMPUTER COMMUNICATION RS 485 TWISTED PAIR POLARITY SENSITIVE BELDEN 8740 OUTDOOR AIR SENSOR TERMINAL...

Page 13: ...13 ZONEXCOMMANDER WIRING OVERVIEW ROOFTOP UNITS UP TO 20 PER COMMAND CENTER...

Page 14: ...dampers based on zone demand The ZonexCommander Plus system can be applied to existing HVAC systems or new installations providing central control of HVAC operations using Windows based ZonexCommande...

Page 15: ...15 ZONEXCOMMANDER PLUS COMPONENT SELECTION GUIDE...

Page 16: ...o be cycled The W1 output signal is connected to the heating device input terminal and the coil of the fan relay This is required for electric heat and gas furnaces with no fan control See Fig 2 on a...

Page 17: ...ommunicate a heat mode call to the is two degrees or more below room temperature ModStat will modulate the damper to 100 open If the room temperature is within two degrees of setpoint the ModStat will...

Page 18: ...Release button 1 Push UP button until display shows H 2 Current setpoint will be displayed 3 Push UP or DN button until desired setpoint is displayed 4 Release button operation A shorted sensor or wir...

Page 19: ...SENSOR CALIBRATION R12 OUTSIDE AIR POWER LED INDICATOR MAIN CONTROL CHIP ZONEX COMMANDER PLUS COMMUNICATION RS 485 TWISTED PAIR POLARITY SENSITIVE BELDEN 8740 SENSOR TERMINAL OA OUTSIDE AIR ONLY TERMI...

Page 20: ...X Wire nuts are never to be used on the communication wire When making connections use screw type terminal strips or solder NOTE for systems with potential electrical interference such as large transf...

Page 21: ...After setting the address the thermostat will automatically go back to normal operation and the setpoint temperature will replace the address number just programmed Manual Operation Adjusting Setpoint...

Page 22: ...hen the space temperaturemeetstheheatsetpoint When configured for Reheat if the space temperature drops 1 below modulate the damper open The heat call will terminate when the space system goes into th...

Page 23: ...t and 75 F cool as measured by the MIX Air sensor in the return air TEMPERATURE LIMITS AND STAGING The RMOD monitors the leaving air temperature for staging and Hi Low 145 F Staging is based on the li...

Page 24: ...NSTALLED STATUS LEDs PWR1 Y1 Y2 W1 and O B W2 G 3 4 5 6 7 8 10 9 11 TERMINAL DESIGNATIONS TX Data transmit RX Data receive RA Return air sensor Gas Electric G Fan output W2 Stage 2 heat output W1 Stag...

Page 25: ...heat elements Heat Pump AHU Addressing Calibration button until the correct address appears and release 2 Energize the FAN only and check RMOD display calibration adjust calibration 4 Return air temp...

Page 26: ...26 RMOD WIRING OVERVIEW All RX communication wires must be connected to the RX terminals All TX communication wires must be connected to the TX terminals The RX and TX wires should never intersect...

Page 27: ...sensor controls low and high temperature limits and heat cool staging RA return air sensor controls unit operation in communication failure mode Keep sensor wires and power wires separate NOTE Shorte...

Page 28: ...gh the 1 4 hole 5 Attach the SENDCOM assembly to the duct or plenum with the sheet metal screws provided 6 Locate the position in the return duct or plenum for the return sensor and drill a 1 4 hole s...

Page 29: ...will be seen on address 1 2 3 and 4 current room temperatures On ZonexCommander Plus systems a SENDCOM cannot be addressed for thermostats 1 2 3 or 4 so start addressing any stand alone equipment in a...

Page 30: ...TION When the RLYCOM is in the Occupied mode the on board relays are energized In the Unoccupied mode the relays are de energized The mode status is displayed on the REVIEW screen of the Commander pro...

Page 31: ...hart 0 1 friction loss per 100 of duct All CFMs listed are approximate For accurate selection use duct sizing table or device MEDIUM PRESSURE STMPD MODSTAT L D W SIZE 6 8 10 12 14 16 6 8 10 12 14 16 D...

Page 32: ...r drive time open and close is 90 seconds RECTANGULAR MEDIUM PRESSURE ZONE DAMPERS Zonex Systems rectangular medium pressure dampers are recommended for systems under 7 5 tons with a maximum different...

Page 33: ...that modulates up and down to control air and throw remain constant This keeps the air hugging the ceiling which maximizes room air mixing and minimizes the waterfall effect ZONE DAMPERS RECTANGULAR D...

Page 34: ...n should be applied to the round pipe and be butted against the hat section do not insulate the motor The motor generates enough heat so that no condensation will develop on it 5 Remember to allow a 1...

Page 35: ...undersize the bypass damper ROUND BYPASS DAMPER SELECTION The Zonex Systems STMPD damper is used for round bypass applications When you know the bypass CFM requirements use the ROUND BYPASS SELECTION...

Page 36: ...2000 13333 14667 16000 36 9000 10500 12000 13500 15000 16500 18000 40 10000 11667 13333 15000 16667 18333 20000 44 11000 12833 14667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 2400...

Page 37: ...ol IPC and air 3 Do not install the bypass damper outside dedicated 24vac 40VA transformer 2 Bypass damper and controller are powered by a recommended for 100 of system CFM system and not undersized B...

Page 38: ...ve Y outputs to unit on the zone control board and to Note 1 To open all dampers it may be necessary to translates to inches of W C one next to the potentiometer The Voltage reading the leads on the C...

Page 39: ...CD into the computer drive and note which drive is being used 2 Click on My Computer 1 Place Systems Software Master CD in the CD drive Installing System Software 4 Under the General Tab for propertie...

Page 40: ...events for each thermostat and RLYCOM Zoned Units Tab Used only with ZonexCommander Plus allocates thermostats to their respective units when multiple units are included in the system SYSTEM START UP...

Page 41: ...store the password NOTE Your password should be retained elsewhere If it is lost the program will have to be re installed and all information re entered Adding Modifying or Deleting Records To add or...

Page 42: ...ord to be deleted f Click on Records g Click on Delete h Click on File then click on Save i Click on Exit to return to the WELCOME Tab Connecting to the Zonex System 1 Click on the Connect Now button...

Page 43: ...nd Settings to place this information into memory Date Time will appear on the upper right of the screen 2 Click on the right or left arrow next to the month and year to select the current month or cl...

Page 44: ...by returning to the REVIEW Tab If the thermostat number you selected is Red it is locked if it is Black it is unlocked If necessary repeat the sequence above to change to desired setting Reviewing Sys...

Page 45: ...setting 6 SENDCOM communications are used to display RA SA temperatures from stand alone units a Place the cursor directly over a Current Room Temperature thermostat number with a SENDCOM attached an...

Page 46: ...isplay thermostat address numbers and names and click on an address b After selecting the desired address the current Occupied and Unoccupied temperature setpoints for that thermostat will be 4 After...

Page 47: ...y a Select the thermostat or RLYCOM address from the pull down menu under Select Thermostat b Click on the radio button next to the day of the week to be scheduled Schedule each day individually After...

Page 48: ...he thermostat address numbers to be assigned to that RMOD one or more addresses may be highlighted NOTE When DIGICOM DIGIHP thermostats or RLYCOM devices are part of the installation they must be addr...

Page 49: ...nex Systems 6 After the logging commences you may minimize the Zonex program in order to use other computer functions but do not turn off the computer or trending program during data collection This w...

Page 50: ...ge to return to Page 1 of the Trending program Then select another thermostat you wish to analyze by using the drop down arrow and the data will be retrieved quickly 13 After the data is collected if...