43
System Setup and Configuration
SYSTEM Screen –
Fig. 10
Stats
2. Select the total number of system devices (up to 20 thermostats and
RLYCOMs
on the Command Center communication buss).
3. The program is equipped with a
System Alarm Deviation
function,
establish out of range temperature criteria from 3-10°. Whenever a
thermostat exceeds the selected deviation from its heating or cooling
setpoints, the current temperature will be highlighted in Yellow on
the REVIEW Screen. If this feature is not required, select
00
to
disable the alert; otherwise, select the temperature deviation.
4. Click on
Send Settings
to place this information into memory.
Date/Time
will appear on the upper right of the screen.
2. Click on the
right or left arrow
next to the month and year to select
the current month or click on today’s date.
3. Click on
current day
to highlight in gray.
4. Click on the
Select Hour
and
Select Minute
down arrow buttons
to select time.
5. Click on the
AM
or
PM
radio button.
6. Click on
Send Settings
to place this information into memory.
7. Verify setting by clicking on the
Clock Setting
button on the top left
of the screen.
SYSTEM START-UP PROCEDURE
Fig. 10
1. Click on the SYSTEMS Tab, and click on the radio button next to
Stats
(see Fig. 11)
.
Fig. 11
or System warning alert
(see Fig. 11)
, which allows the user to
1. Click on the
Date/Time
radio button
(see Fig. 12)
, and a calendar
Fig. 12