ELECTRICAL PRECAUTIONS

  Before servicing a pump, always shut off the main power breaker to the panel and then disconnect the 

pump - making sure you are wearing insulated protective sole shoes and are not standing in water. Under flooded conditions, contact your local electric 

company or a qualified licensed electrician for disconnecting electrical service prior to pump removal. 

 Submersible pumps contain oils which become pressurized and hot under operating conditions -

 allow 2-1/2 hours after disconnecting before 

attempting service.

CONDITION

A.   Pump will not start or run.

 

          COMMON 

CAUSES

B.  Motor overheats and trips overload or blows fuse.

 

-  Incorrect Voltage

 

-  Unbalanced power source

 

-  Incorrect motor rotation

 

-  Negative or low head

 

-  Excessive water temperature

 

-  Impeller or seal mechanically bound

 

-  Defective capacitor or relay

 

-  Motor shorted

 

-  Lost one line in a Three Phase unit

C.   Pumps starts and stops too often.

 

-  Check valve stuck open

 

-  Level controls out of adjustment

 

-  Thermal overload switch out of 

 

  adjustment or defective

 

-  Pit too small

D.   Pump will not shut off.

 

-  Debris under float switch

 

-  Float travel obstructed

 

-  Defective or damaged float switch 

 

-  Magnetic starter contacts shorted

 

-  Air lock - check vent hole

E. Pump operates but delivers little or no water.

 

-  Check for plugged Pump housing, discharge  

 

 

  pipe or sticking check valve

 

-  Vent hole clogged or not drilled

 

-  Discharge head exceeds pumps capacity

 

-  Low or incorrect voltage

 

-  Incorrect motor rotation

 

-  Defective capacitor

F.   Drop in head and/or capacity after a period or use.

 

-  Increase Pipe Friction

 

-  Clogged line or check valve

 

-  Abrasive material & chemical, 

 

  deteriorated impeller and pump housing

If the above check list does not uncover the problem, consult the factory - Do not attempt to service or otherwise disassemble pump.

Service Checklist & Trouble Shooting

 

Steps 

Check Voltage At 

If No Voltage 

If Voltage

 

No. 1 

Line terminals in pump’s 

Check Disconnect switch, line 

Proceed to No. 2

 

 

control panel 

fuse, and/or circuit breakers 

  

L

1

 - L

2

 - L

3

 (3 Phase) 

in power supply circuit.

 

No. 2 

Pump motor terminals in 

Check for control circuit 

Check starting relay 

 

 

pump’s control panel  

voltage. Check out magnetic 

and capacitor (1 

  

T

1

 - T

2

 - T

3

 

starter contacts, thermal 

phase units). Check

    

 

overloads, and float switches 

pump for ground, 

 

 

 

 

and binding impeller

© Copyright 2023 Zoeller

®

 Co. All rights reserved.

8

These are the original installation instructions.

Summary of Contents for E611

Page 1: ...l on 600 Series pumps Should further assistance be necessary please call our Product Support Department at 1 800 928 PUMP 7867 Table of Contents Safety Instructions 1 Limited Warranty 2 Performance Da...

Page 2: ...ther liability in connection with our products Contact Manufacturer at 3649 Cane Run Road Louisville Kentucky 40211 Attention Customer Service Department to obtain any needed repair or replacement of...

Page 3: ...ver sufficient voltage to the pump motor But more importantly they could present a safety hazard if the insulation were to become damaged or the connection end were to fall into the sump 4 Make sure t...

Page 4: ...ump housing Be sure that this hole is cleared during any servicing 7 Vent gases and odors to the atmosphere through vent pipe per Local and State codes 8 Secure power cord to avoid entanglement with v...

Page 5: ...for mounting these starting components 2 All pumps require overload protection in panel Use with approved motor control that matches motor input in full load amperes with overload element s selected o...

Page 6: ...allation All single phase models require start capacitor run capacitor and relay in the circuit to start and operate properly These components can be purchased separately or prewired in Zoeller Pump C...

Page 7: ...teringabasinshouldbewearingaharnesswithsafetyrope extending to the surface so that they can be pulled out in case of asphyxiation Sewage water gives off methane and hydrogen sulfide gases both of whic...

Page 8: ...h Float travel obstructed Defective or damaged float switch Magnetic starter contacts shorted Air lock check vent hole E Pump operates but delivers little or no water Check for plugged Pump housing di...

Page 9: ...ump Company http reg zoellerpumps com N mero de modelo ___________ C digo de fecha __________ N mero de serie Bomba 1 ____________ Bomba 2 ___________ Simplex N P de Panel ___________________________...

Page 10: ...nto lodo alquitr n hidrocarburos derivados de hidrocarburos aceite gasolina solventes etc u otras sustancias abrasivas o corrosivas toallas para lavar o productos sanitarios femeninos etc en todas las...

Page 11: ...s bombas sumergibles con capacidad para manejar desechos s lidos de diferentes tama os tengan un dise o para entrada en la parte inferior de modo que se reduzcan los atascos y las fallas del sello Si...

Page 12: ...or de la bomba NOTA Elagujerodeber estardebajodelacubiertadel contenedorylimpiarseperi dicamente Durantelosperiodos de funcionamiento de la bomba se ver un chorro de agua que sale del respiradero Perf...

Page 13: ...eber ncumplirsetodoslosdem srequerimien tos de la NEC consulte los art culos 500 501 y 502 y los dem s que correspondan Instrucciones de cableado Las bombas trif sicas no son autom ticas Para su opera...

Page 14: ...631 641 651 Y 611 621 CON REL GE DESPU S DEL 10 1 07 Roc e una capa de aceite anticorrosivo a las superficies que no est n pintadas El impulsor debe girarse cada seis meses para mantener los sellos l...

Page 15: ...da de seguridad que llegue hasta la superficie para poder sacarlas en caso de asfixia Las aguas negras despiden gas metano y sulfuro de hidr geno que pueden ser altamente t xicos Lainstalaci nyrevisi...

Page 16: ...quema el fusible Voltaje incorecto Fuente de poder desbalanceada Rotaci n incorrecta del motor Carga baja o nagativa Temperatura del agua demasiado alta El impulsor o el sello est n pegados mec nicam...

Page 17: ...CAUSENT des blessures corporelles graves la mort ou des dommages mat riels importants Il avertit des dangers qui PEUVENT causer des blessures corporelles graves la mort ou des dommages mat riels impor...

Page 18: ...ter la responsabilit en notre nom pour nos produits Prendre contact avec le Fabricant 3649 Cane Run Road Louisville KY 40211 Attention Customer Support pour obtenir des r parations des pi ces de rempl...

Page 19: ...gues ou de trop faible capacit ne fournissent pas la tension n cessaire au moteur de la pompe et ellespeuvent tredangereusessil isolantestendommag ousil extr mit avec le branchement tombe dans un endr...

Page 20: ...ompe dispose d un trou d vent 7 Doit tre nettoy avant le etretien Les gaz et les odeurs rejet s dansl atmosph reparletuyaud ventd apr slescodeslocaux et nationaux 8 S curiser le cordon d alimentation...

Page 21: ...les ressources n cessaires l installation de ces composantes de d marrage 2 Toutes les pompes n cessitent une protection de surcharge dans le panneau N utiliser qu avec une commande moteur quivalente...

Page 22: ...er une d formation permanente Installation monophas e Tous les mod les monophas s n cessitent un condensateur de d marrage un condensateur de fonctionnement et un relai dans le circuit afin de d marre...

Page 23: ...deux tre fortement toxiques L installation et la v rification de l quipement lectrique doivent tre faites par un lectricien qualifi Il ne faut jamais soulever la pompe par le cordon d alimentation AVE...

Page 24: ...de blocage de l impulseur CAUSES FR QUENTES B Le moteur surchauffe et d clenche la surcharge ou grille un fusible Mauvaise tension Source d alimentation d s quilibr e Mauvaise rotation du moteur Press...

Reviews: