Zimmer GmbH • Im Salmenkopf 5 •
77866 Rheinau, Germany •
+49 7844 9138 0 • www.zimmer-group.com
EN / 2023-07-07
DDOC01932 / -
34
INSTALLATION AND OPERATING INSTRUCTIONS:
MFS02-S-KHC-IL
Device specific
Index
dec (hex)
Name
Format
(Offset)
Length
Access
1
Default
Value
Value / Range
Remark [Unit]
16393 (0x4009)
Qint.7 Configuration Record
4 Byte
rw
1 (0x01)
Switchpoint Logic
Bit (24)
8 Bit
rw
0
0 = Not inverted
1 = Inverted
2 (0x02)
Switchpoint Mode
Bit (16)
8 Bit
rw
0
0 = Deactivated
1 = Single Point Mode
2 = Window Mode
3 = Two Point Mode
129 = Cylinder Switch Mode
3 (0x03)
Switchpoint
Hysteresis
Bit (0)
16 Bit
rw
70
[×10μm]
16394 (0x400A)
Qint.8 SP1 / SP2
Record
4 Byte
rw
1 (0x01)
SP1
Bit (16)
16 Bit
rw
0
Setpoint 1
2 (0x02)
SP2
Bit (0)
16 Bit
rw
0
Setpoint 2
16395 (0x400B)
Qint.8 Configuration Record
4 Byte
rw
1 (0x01)
Switchpoint Logic
Bit (24)
8 Bit
rw
0
0 = Not inverted
1 = Inverted
2 (0x02)
Switchpoint Mode
Bit (16)
8 Bit
rw
0
0 = Deactivated
1 = Single Point Mode
2 = Window Mode
3 = Two Point Mode
129 = Cylinder Switch Mode
3 (0x03)
Switchpoint
Hysteresis
Bit (0)
16 Bit
rw
70
[×10μm]
16512 (0x4080)
MDC Descr
Record
11 Byte
ro
1 (0x01)
Lower Limit
Bit (56)
32 Bit
ro
-2500
-2147482880...2147482880 = Permissible values
for the Detection range
Lower value
measurement range
3 (0x03)
Upper Limit
Bit (24)
32 Bit
ro
2500
-2147482880...2147482880 = Permissible values
for the Detection range
Lower value
measurement range
3 (0x03)
Unit code
Bit (8)
16 Bit
ro
1010
1010 = Distance [m]
4 (0x04)
Scale
Bit (0)
8 Bit
ro
-5
-128...127 = Range shifting (10^scale)
17341 (0x43BD)
FW Password
String
16 Byte
wo
17342 (0x43BE)
HW ID Key
String
32 Byte
ro
17343 (0x43BF)
Bootmode Status
UInt
8 Bit
ro
0 = Bootloader is inactive
1 = Bootloader is active
Standard command
Index
dec (hex)
Access
1
Value
Name
Remark [Unit]
2 (0x02)
System Command
wo
65
SP1 Single Value Teach
66
SP2 Single Value Teach
75
Dynamic Teach Start
76
Dynamic Teach Stop
77
Dynamic Teach Apply
79
Teach Cancel
80
Start unlocking sequence
81
Unlocking command 1
82
Unlocking command 2
128
Device Reset
Performs a system restart.
All read-only parameter
are rejected
129
Application Reset
Reset all application
specific values except the
identification
parameters
130
Restore Factory Settings
All default parameter are
reloaded
192
Reset trained algorithm
parameter
Reset for all actuator
specific values related to
position
calculation of MPS-G
228
Reset diagnostics
parameter
Resets operating hours,
power cycles, cycle count
and total actuator travel
229
Reset all present alerts
1 ro = read only, wo = write only, rw = read/write
2 COM values specify the bitrate (see IO-Link specification): COM1 (4,8 kbit/s), COM2 (38,4 kbit/s), COM3 (230,4 kbit/s)