INSTALLATION AND OPERATING INSTRUCTIONS:
MFS02-S-KHC-IL
EN / 2023-07-07
11.1.2 Manual teach-in
Manual teach-in is recommended when two or three randomly placed switch points should be detected within the
measuring range.
INFORMATION
The end positions can only be taught in separately. After teaching in an end position, the menu is closed and
must be reopened.
►
Press the Teach-in button three times for approx. 0.5 seconds.
Ö
The Teach menu for manual teach-in opens.
►
If you want to exit the Teach menu again, repress the Teach-in button for approx. 0.5 seconds.
►
To continue, press the Teach-in button for approx. 1.5 seconds.
Ö
Manual teach-in starts.
►
Move the piston to the first end position in the negative direction or line direction.
►
Press the Teach-in button for approx. 1.5 seconds.
Ö
If no switch point was detected by the sensor, both external LED displays light up yellow and the Teach menu is closed
without changes.
►
If the attempt fails, repeat the process until the switch point has been detected.
Ö
If the switch point was detected by the sensor, the PWR LED display lights up green and the MR LED display lights up
yellow while the magnet is located within the measuring range.
Ö
The position is confirmed and saved and the Teach menu closes.
►
Press the Teach-in button three times for approx. 0.5 seconds to teach in another switch point.
Ö
The Teach menu for manual teach-in opens.
►
If you want to exit the Teach menu again, repress the Teach-in button for approx. 0.5 seconds.
►
To continue, press the Teach-in button for approx. 1.5 seconds.
Ö
Manual teach-in starts.
►
Press the Teach-in button for approx. 0.5 seconds to set the next position.
►
Move the piston to the other end position in the positive direction or mounting screw direction.
►
To confirm the position, press the Teach-in button for approx. 1.5 seconds.
Ö
The position is saved and the Teach menu closes.
11.2 Resetting switch points
►
To reset the measuring range to the default settings, press the teach-in button for 3–5 seconds.
Ö
The external LED displays light up in yellow in sequence.
Ö
After 3–5 seconds, only the PWR LED display lights up green.
Ö
The measuring range has been reset.