11.4.6 Selecting the switch point mode
After manual teach-in of switch points 1–8, you can select between four different switch point modes.
Single point mode:
The switch-on and switch-off point are defined
by Qint.SP1 in this mode. In the positive
direction, the signal for all positions is high after
the switch-on point. The signal switches to low
as soon as the piston has passed the switch-on
point and the switch point hysteresis.
2
1
+25 mm
-25 mm
ON
OFF
-25 mm
ON
ON
ON
OFF
OFF
ON
OFF
+25 mm
ON
ON
ON
ON
OFF
Qint.SP1
Qint.SP1
1
Movement direction of piston
2
Hysteresis
Window mode:
In this mode, the switch points 1 and 2 define a
window in which the signal is continuously high.
The switch point hysteresis is located symmet-
rically around the switch points. When the
piston moves in the positive direction or in the
direction of the mounting screw of the sensor,
the signal within the hysteresis at switch point 1
is low and high at switch point 2. In the negative
direction, it is low at switch point 2 within the
hysteresis and high at switch point 1.
2
1
3
+25 mm
Qint.SP2
-25 mm
ON
OFF
-25 mm
OFF
ON
ON
OFF
OFF
ON
OFF
+25 mm
OFF
OFF
ON
ON
OFF
Qint.SP1
Qint.SP2
Qint.SP1
1
Movement direction of piston
2
Hysteresis
3
Switch window