SR981S/SR982S operation manual of solar pump station
Page 53 of 85
Setup steps:
To access main menu TEMP, then select submenu MAX1,
“MAX1 60
o
C” shows on the screen.
►Press “SET” button, parameter “60
o
C” blinks
►Press
“
” button to adjust the value of maximum
temperature of
tank ,
adjustable range is (
MIN1+2
o
C)
~
95
o
C, default set is 60
o
C
► Press “ESC”
button to exit the menu or wait for 20 seconds to exit, parameters are
saved automatically.
8.4.9 MIN1 Minmium switch-on temperature for heat transfer between tank and
heat return
Setup steps:
To access main menu TEMP, then select submenu MIN1,
“MIN1 30
o
C” shows on the screen.
►Press “SET” button, parameter “30
o
C” blinks
►Press
“
” button to adjust the value of maximum
temperature of
tank,
adjustable range is
10
o
C
~
(MAX1-2
o
C), default set is 30
o
C
► Press “ESC”
button to exit the menu or wait for 20 seconds to exit, parameters are
saved automatically.
8.4.10 MAX2 Maximum switch-off temperature for heat transfer between heat
exchanger and tank
Description:
Example with system 12
In the case that collector T1, heat exchanger temperature T4 and tank T2 all meet the
switch-on condition, when value of T4 is between the minimum switch-on temperature
MIN2 and its maximum switch-off temperature MAX2, P1 and P2 pump are triggered at the
same time; when T4 exceeds the MAX2, then P1 is ceased. When T4 drops below its
MIN2, then P2 is ceased.
In the case that collector T1, heat exchanger temperature T4 and tank T2 all meet the