Parameter
Factory set-
ting
Cot 1
Cot 2
Cot 3
Cot 4
Cot 5
Information
Heating1 curve
ON
Heating1 start
0.0 K
Heating1 knick1
-1.0 K
Heating1 knick2
-1.5 K
Heating1
fi
nal
-2.0 K
Heating2 curve
OFF
Heating2 start
24.0
°
C
Heating2knick1
23.0
°
C
Heating2knick2
22.0
°
C
Heating2
fi
nal
21.0
°
C
- = Only display, no adjustment possible
* = at alternative temperature source (E2, E3 or Bus) setting as Setpoint
10.2
Installation menu
Information
The settings made in installation must be noted here as a reminder!
The settings in the
“
installation menu
”
are priority basic settings that must be made during start-up
operation. Make these settings only if you have an exact understanding of the device functions and
system functions. Subsequent modi
fi
cations must be coordinated with your electrician.
We are never liable for damage or harm caused by improper operation or insuf
fi
cient knowledge.
Enter the individual settings here for tracing!
Parameter
Factory set-
ting
Cot 1
Cot 2
Cot 3
Cot 4
Cot 5
Information
Ventilation
Exhaustair rate
10.0 %
Variant of peak load
|
1
|
= switch on by relay
|
2
|
= two regulated fans of different
size
|
3
|
= two regulated fans of same size
Msco
OFF
MSCO value
-5.0 K
Startvoltage
15 %
Peak load On
50 %
Peak load min.
20 %
Peak load var.
OFF
humidity control
OFF
RH cooling
- - - -
Shutter
Shutter input
0
input for Control Shutter
|
0
|
= E1 /
|
1
|
= E2 /
|
2
|
= Bus /
|
3
|
=
E3
Kl. Val<Set=+
OFF
Ventilation link
OFF
Heating1
H1 Mode
1
Mode for H1
|
OFF
|
|
1
|
= Relays
|
2
|
= 0...10 V
H1 Input
0
H1 Val<Set=+
ON
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ-L
Menu tables
L-BAL-E139-GB 2022/03 Index 006
Part.-No.
75/92