7.15
|
Installation
|
Motorsetup
7.15.1
Menu
“
Motorsetup
”
Motor Setup
Menu group Motor Setup
Attention!
Settings for U/f characteristic may only be made when no motor modulation is present!
Parameter
Factory setting
User Setting
MotorRatedCurr.
6.0 A
MotorRatedVolt.
230 V
Edgefrequency
50.0 Hz
Max. Frequency
50.0 Hz
Rampup time
10 sec
Rampdown time
10 sec
Shutdown Freq.
10.0 Hz
Startvoltage
8 %
VF quadratic
EIN
Current limit
120 %
DC brake mode
1
DC brake time
5 sec
DC brake level
10 %
Boost Value
15.0 %
Suppression1
AUS
Range1 min.
- - - -
Range1 max.
- - - -
Suppression2
AUS
Range2 min.
- - - -
Range2 max.
- - - -
Suppression3
AUS
Range3 max.
- - - -
Range3 max.
- - - -
7.15.2
Setting motor rated current
MotorRatedCurr.
MotorRatedCurr.
Possible setting for the motor rated current.
The setting for the
“
DC brake level
”
(
setting brake behaviour) refers to this setting.
Setting range: 0.0...device rated current / A
Factory setting: device rated current
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ-L
The Installation menu
L-BAL-E139-GB 2022/03 Index 006
Part.-No.
48/92